background image

11

GB

D

F

I

NL

E

P

GR

RU

TR

Example of a group operation system with multiple heat source units (Shielding wires and address setting are

necessary.)

<Examples of Transmission Cable Wiring>

[Fig. 9.3.1] M-NET Remote Controller (P.4)

[Fig. 9.3.2] MA Remote Controller (P.4)

A

Group 1

B

Group 3

 

C

Group 5

D

Shielded Wire

E

Sub Remote Controller

(  ) Address

2

Wiring examples

Controller name, symbol and allowable number of controllers.

2. Remote control cables

Kind of remote control cable

Cable diameter

Remarks

2-core cable (unshielded)
0.3 to 1.25 mm

2

When 10 m is exceeded, use cable with the
same specifications as (1) Transmission line
wiring

9. Wiring

9.1. Caution

1

Follow ordinance of your governmental organization for technical standard re-
lated to electrical equipment, wiring regulations and guidance of each electric
power company.

2

Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or
more) apart from power source wiring so that it is not influenced by electric
noise from power source wiring. (Do not insert transmission line and power
source wire in the same conduit.)

3

Be sure to provide designated grounding work to heat source unit.

4

Give some allowance to wiring for electrical part box of indoor and heat source
units, because the box is sometimes removed at the time of service work.

5

Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will be burnt out.

6

Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor trans-
mitting and receiving will cause erroneous operations.

7

Only the transmission line specified should be connected to the terminal block
for heat source unit transmission.
(Transmission line to be connected with indoor unit : Terminal block TB3 for
transmission line, Other : Terminal block TB7 for centralized control)
Erroneous connection does not allow the system to operate.

8

In case to connect with the upper class controller or to conduct group opera-
tion in different refrigerant systems, the control line for transmission is required
between the heat source units each other.
Connect this control line between the terminal blocks for centralized control.
(2-wire line with no polarity)
When conducting group operation in different refrigerant systems without con-
necting to the upper class controller, replace the insertion of the short circuit
connector from CN41 of one heat source unit to CN40.

9

Group is set by operating the remote controller.

0

The unused knockout holes should be closed and the opening of refrigerant
pipes, water pipes, power source and transmission wires should be filled with
putty and so on to prevent from rain. (field construction)

9.2. Control box and connecting position of

wiring

1. Connect the indoor unit transmission line to transmission terminal block (TB3),

or connect the wiring between heat source units or the wiring with the central
control system to the central control terminal block (TB7).

Name

heat source unit controller
BC Controller
Indoor Unit Controller
Remote Controller

Symbol

OC

BC

IC

RC

Allowable number of controllers

One controller for one OC
Two to ten controllers for one OC
Maximum of two per group

When using shielded wiring, connect shield ground of the indoor unit transmis-
sion line to the earth screw (

) and connect shield ground of the line between

heat source units and the central control system transmission line to the shield
(S) terminal of the central control terminal block (TB7) shield (S) terminal. In
addition, in the case of heat source units whose power supply connector CN41
has been replaced by CN40, the shield terminal (S) of terminal block (TB7) of
the central control system should also be connected to the ground (

).

[Fig. 9.2.1] (P.4)

A

Power source

B

Transmission line

2. Conduit mounting plates (ø27) are being provided. Pass the power supply and

transmission wires through the appropriate knock-out holes, then remove the
knock-out piece from the bottom of the terminal box and connect the wires.

3. Fix power source wiring to terminal box by using buffer bushing for tensile

force (PG connection or the like).

9.3. Wiring transmission cables

1

Types of control cables

1. Wiring transmission cables

Types of transmission cables: Shielding wire CVVS or CPEVS

Cable diameter: More than 1.25 mm

2

Maximum wiring length: Within 200 m

<Wiring Method and Address Settings>

a. Always use shielded wire when making connections between the heat source unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.

b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each heat source unit (OC) to terminals M1,

M2 and terminal S on the transmission cable block of the indoor unit (IC).

c.

Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).

d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the heat source unit (OC).

e. On one heat source unit only, change the jumper connector on the control panel from CN41 to CN40.

f.

Connect the terminal S on the terminal block for central control (TB7) for the heat source unit (OC) for the unit into which the jumper connector was inserted into CN40
in Step above to the ground terminal 

 in the electrical component box.

g. Set the address setting switch as follows.
*

To set the heat source unit address to 100, the heat source address setting switch must be set to 50.

Unit

Range

Setting Method

IC (Main)

01 to 50

Use the most recent address within the same group of  indoor units

IC (Sub)

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be
in sequence with the IC (Main)

Heat source Unit

51 to 100

Use the most recent address of all the indoor units plus 50

BC controller

51 to 100

Heat source unit address plus 1

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.

Summary of Contents for CITY MULTI PQRY-P-YMF-C Series

Page 1: ...r un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unid...

Page 2: ...view A Piping space for left piping B Heat source unit C Service space front side D Top view D Anti vibration pad E Concrete base E Piping space for top piping F Piping space for left piping G Heat source unit H Front view A Water circulation pipe B Close valve C Close valve D Water outlet E Refrigerant piping F Y type strainer G Water inlet H Drain pipe A Short circuit wire Connected before deliv...

Page 3: ...g f h A BC controller B Indoor unit 20 140 C Indoor unit 200 250 A Valve stem B Stopper pin C Packing Accessory D Connecting pipe Accessory E Open Operate slowly F Cap copper packing G Service port H Flare nut I ø19 05 J ø25 4 PQRY P200 ø28 58 PQRY P250 K Field piping L Close packed packing M Hollow packing A System analyzer B Lo Knob C Hi Knob D Ball valve E Low press pipe F High press pipe G Ser...

Page 4: ...C 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 MA MA MA OC M1M2 M1M2S TB7 TB3 53 OC c 1 c4 c 3 BC M1M2S 52 BC M1M2S 54 S Power Supply Unit S MJ103 L3 L 6 L 7 L4 c 3 A B A B A B M1M2 M1M2 c 1 c 1 c2 c2 A B A Steel wire B Piping C Asphaltic oily mastic or aspha...

Page 5: ...e to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heater stove oven or other hea...

Page 6: ...acuum pump with a reverse flow check valve The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base refrigerant recovery equipment If the conventional refrigerant and refrigerator...

Page 7: ...ater inlet head at the middle of the unit Use this for maintenance etc In addition do not allow any of the unit s electrical parts such as the solenoid valve coil or compressor power supply to become wet Install a back flow prevention valve on the pump and a flexible joint to prevent excess vibration Use a sleeve to protect the pipes where they go through a wall Use metal fittings to secure the pi...

Page 8: ... circuit connection City Multi R2 Series is constituted by an end branching system in which the refrig erant piping from heat source unit is branched at BC controller and connected to each indoor unit The connection method adapted is flange connection for low pressure pipe and flare connection for high pressure pipe between heat source unit and BC controller and flare connection between BC control...

Page 9: ...8 3 1 P 3 A Nitrogen gas B To indoor unit C System analyzer D Lo Knob E Hi Knob F Stop valve G Low press pipe H High press pipe I Heat source unit J Service port For R407C models The method of conducting the airtight test is basically the same as for R22 models However since the restrictions have a large affect on deterioration of the refrigera tor oil always observe them Also with nonazeotropic r...

Page 10: ...el wire Adhesive Heat resistant polyethylene foam Adhesive tape Indoor Vinyl tape Floor exposed Water proof hemp cloth Bronze asphalt Heat source Water proof hemp cloth Zinc plate Oily paint Note When using polyethylene cover as covering material asphalt roofing shall not be required No heat insulation must be provided for electric wires Fig 8 4 2 P 4 A Liquid pipe B Gas pipe C Electric wire D Fin...

Page 11: ...roller Symbol OC BC IC RC Allowable number of controllers One controller for one OC Two to ten controllers for one OC Maximum of two per group When using shielded wiring connect shield ground of the indoor unit transmis sion line to the earth screw and connect shield ground of the line between heat source units and the central control system transmission line to the shield S terminal of the centra...

Page 12: ...1 L2 L3 L4 and L1 L2 L3 L5 and L1 L2 L6 L7 500 m 1 25 mm2 or more Max transmission cable length L1 and L3 L4 and L3 L5 and L6 and L2 L6 and L7 200 m 1 25 mm2 or more Remote controller cable length r1 r2 r3 r4 10 m 0 3 to 1 25 mm2 If the length exceeds 10 m use a 1 25 mm2 shielded wire The length of this section L8 should be included in the calculation of the maximum length and overall length 2 MA ...

Page 13: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Reviews: