36
OCH610G
Switch
Pole
Function
Operation by switch
Effective
timing
Remarks
ON
OFF
SW11
1s digit
address
setting
SW12
10s digit
address
setting
Rotary switch
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
SW12
10
SW11
1
Address setting
should be done
when M-NET
remote controller is
being used.
Before
power
supply
ON
Indoor controller board
<Initial setting>
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
SW12
SW11
SW14
Connection
No.
setting
Rotary switch
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
SW14
This is the switch
to be used when
the indoor unit is
operated with R2
series outdoor unit
as a set.
Indoor controller board
<Initial setting>
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
SW14
SW21
Function
Setting
1
Setting the ceiling height
Depending on the combination
of SW21-1 and SW21-2.
Refer to the <Table E> below.
Under
suspension
Indoor controller board
<Initial setting>
ON
OFF
1 2 3 4 5 6
2
Setting the ceiling height
3
Setting the number of air outlet
Depending on the combination
of SW21-3 and SW21-4.
Refer to the <Table E> below.
4
Setting the number of air outlet
5
Setting for optional parts
Option
Standard
6
Not used
Not used
Not used
Continue to the next page
PLFY-EP06/08/12/15/18/24/30NEMU-E
PLFY-EP18NEMU-E1
PLFY-EP36/48NEMU-E
Silent
Standard
High ceiling
Silent
Standard
High ceiling
SW21-1
SW21-2
SW21-1
SW21-2
SW21-1
SW21-2
SW21-1
SW21-2
SW21-1
SW21-2
SW21-1
SW21-2
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
4 direction
SW21-3
OFF
8.2 ft [2.5 m]
8.9 ft [2.7 m]
11.5 ft [3.5 m]
8.9 ft [2.7 m]
10.5 ft [3.2 m]
14.8 ft [4.5 m]
SW21-4
ON
3 direction
SW21-3
OFF
8.9 ft [2.7 m]
9.8 ft [3.0 m]
11.5 ft [3.5 m]
9.8 ft [3.0 m]
11.8 ft [3.6 m]
14.8 ft [4.5 m]
SW21-4
OFF
2 direction
SW21-3
ON
9.8 ft [3.0 m]
10.8 ft [3.3 m]
11.5 ft [3.5 m]
10.8 ft [3.3 m]
13.1 ft [4.0 m]
14.8 ft [4.5 m]
SW21-4
OFF
<Table E>
Note: The setting with
indicates the initial setting; To change it to other than
, switch setting is necessary.