25
OCH610G
25
Control Mode
Control Details
Remarks
3. Drain pump
3-1. Drain pump control
• The drain pump will always run when the unit is in COOL or DRY mode.
(Regardless of the thermo ON/OFF)
• Whenever the operation is changed over to the other modes (including Stop), the drain
pump will stop pumping after approximately 3 minutes.
Float switch control
• Float switch control judges whether the sensor is in the air or in the water by turning the
ÀRDWVZLWFK212))
,QWKHZDWHU'HWHFWHGWKDWWKHÀRDWVZLWFKLV21IRUVHFRQGV
,QWKHDLU'HWHFWHGWKDWWKHÀRDWVZLWFKLV2))IRUVHFRQGV
ON
OFF
15 s
15 s
15 s
1 min 30 s
1 min 30 s
Float SW
In the water
In the air
In the water
Error
postponement
Drain pump
abnormal
4. Vane
(up/down vane
change)
(1) The initial vane setting for COOL mode will be the horizontal position.
(2) Vane position:
+RUL]RQWDOĺ'RZQZDUG$ĺ'RZQZDUG%ĺ'RZQZDUG&ĺ'RZQZDUG'ĺ6ZLQJĺ$XWR
(3) Restriction of the downward vane setting
If the vane position is set to Downward A/B/C/D in [Med1], [Med2], or [Low], the vane will
return to the horizontal position after 1 hour has passed.
•
"ONLY 1 Hr" appears on
the wired remote controller.