OCH710
Model
PKFY-P32VLM-E
PKFY-P32VLM-ET
PKFY-P32VLM-TH
PKFY-P40VLM-E
PKFY-P40VLM-ET
PKFY-P40VLM-TH
PKFY-P50VLM-E
PKFY-P50VLM-ET
PKFY-P50VLM-TH
Power source
1-phase 220-240 V 50 Hz, 1-phase 220-230 V 60 Hz
Cooling capacity *1
(Nominal) *1
*1
kW
3.6
4.5
5.6
kcal/h
3100
3900
4800
BTU/h
12300
15400
19100
Power input
kW
0.04
0.04
0.05
Current input
A
0.35
0.35
0.45
Heating capacity *2
(Nominal) *2
*2
kW
4.0
5.0
6.3
kcal/h
3400
4300
5400
BTU/h
13600
17100
21500
Power input
kW
0.03
0.03
0.04
Current input
A
0.30
0.30
0.40
External finish(Munsell No.)
Plastic (0.7PB 9.2/0.4)
External dimension H x W x D
mm
299 × 773 × 237
299 x 898 x 237
inch
11-25/32 x 30-7/16 x 9-11/32
11-25/32 x 35-3/8 x 9-11/32
Net weight
kg (lb)
11(25)
13(29)
Heat exchanger
Cross fin (Aluminum fin and copper tube)
Fan
Type x Quantity
Line flow fan x 1
External
static press
Pa
(mmH2O)
0(0)
Motor type
DC motor
Motor output
kW
0.03
Driving mechanism
Direct driven
Airflow rate
(Low-Mid2
-Mid1-High)
m
3
/min
4.3-5.4-6.9-8.4
6.3-7.4-8.6-10.0
6.8-8.3-10.2-12.4
L/s
72-90-115-140
105-123-143-167
113-138-170-207
cfm
152-191-244-297
222-261-304-353
240-293-360-438
Noise level
(Low-Mid2-Mid1-High)
(measured in anechoic room)
dB <A>
24-31-37-41
29-34-37-40
31-36-41-46
Insulation material
Polyethylene sheet
Air filter
PP Honeycomb
Protection device
Fuse
Refrigerant control device
LEV
Connectable outdoor unit
R410A CITY MULTI
Diameter of
refrigerant pipe
Liquid
mm
(in)
{
6.35 (
{
1/4)
Gas
mm
(in)
{
12.7 (
{
1/2)
Field drain pipe size
mm
(in)
I.D.16 (5/8)
Standard attachment
Installation Manual, Instruction Book
Optional parts
DRAIN PUMP KIT
PAC-SK01DM-E
EXTERNAL LEV BOX
PAC-SG95LE-E
Remark
Details on foundation work, duct work, insulation work, electrical wiring, power source
switch, and other items shall be referred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without
notice.
Notes:
*
1.Nominal cooling conditions (subject to JIS B8615-1)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)
Pipe length: 7.5 m (24-9/16 ft), Level difference: 0 m (0 ft)
*
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft), Level difference: 0 m (0 ft)