13
OCH710
13
3
SPECIFICATION
3-1. SPECIFICATIONS
Model
PKFY-P10VLM-E
PKFY-P10VLM-ET
PKFY-P15VLM-E
PKFY-P15VLM-TH
PKFY-P15VLM-ET
PKFY-P20VLM-E
PKFY-P20VLM-TH
PKFY-P20VLM-ET
PKFY-P25VLM-E
PKFY-P25VLM-TH
PKFY-P25VLM-ET
Power source
1-phase 220-240 V 50 Hz, 1-phase 220-230 V 60 Hz
Cooling capacity *1
(Nominal) *1
*1
kW
1.2
1.7
2.2
2.8
kcal/h
1000
1500
1900
2400
BTU/h
4100
5800
7500
9600
Power input
kW
0.02
0.02
0.02
0.03
Current input
A
0.20
0.20
0.20
0.25
Heating capacity *2
(Nominal) *2
*2
kW
1.4
1.9
2.5
3.2
kcal/h
1200
1600
2200
2800
BTU/h
4800
6500
8500
10900
Power input
kW
0.01
0.01
0.01
0.02
Current input
A
0.15
0.15
0.15
0.20
External finish(Munsell No.)
Plastic (0.7PB 9.2/0.4)
External dimension H x W x D
mm
299 × 773 × 237
inch
11-25/32 x 30-7/16 x 9-11/32
Net weight
kg (lb)
11(25)
Heat exchanger
Cross fin (Aluminum fin and copper tube)
Fan
Type x Quantity
Line flow fan x 1
External
static press
Pa
(mmH2O)
0(0)
Motor type
DC motor
Motor output
kW
0.03
Driving mechanism
Direct driven
Airflow rate
(Low-Mid2
-Mid1-High)
m
3
/min
3.3-3.5-3.8-4.2
4.0-4.2-4.4-4.7
4.0-4.4-4.9-5.4
4.0-4.6-5.4-6.7
L/s
55-58-63-70
67-70-73-78
67-73-82-90
67-77-90-112
cfm
117-124-134-148
141-148-155-166
141-155-173-191
141-162-191-237
Noise level
(Low-Mid2-Mid1-High)
(measured in anechoic room)
dB <A>
22-24-26-28
22-24-26-28
22-26-29-31
22-27-31-35
Insulation material
Polyethylene sheet
Air filter
PP Honeycomb
Protection device
Fuse
Refrigerant control device
LEV
Connectable outdoor unit
R410A CITY MULTI
Diameter of
refrigerant pipe
Liquid
mm
(in)
{
6.35 (
{
1/4)
Gas
mm
(in)
{
12.7 (
{
1/2)
Field drain pipe size
mm
(in)
I.D.16 (5/8)
Standard attachment
Installation Manual, Instruction Book
Optional parts
DRAIN PUMP KIT
PAC-SK01DM-E
EXTERNAL LEV BOX
PAC-SK17LE-E
PAC-SG95LE-E
Remark
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall
be referred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
*
1.Nominal cooling conditions (subject to JIS B8615-1)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)
Pipe length: 7.5 m (24-9/16 ft), Level difference: 0 m (0 ft)
*
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft), Level difference: 0 m (0 ft)
Unit converter
kcal/h = kW × 860
Btu/h = kW × 3,412
cfm = m
3
/min × 35.31
lb = kg/0.4536
Note: Above specification
data is subject to
rounding variation.