IV
Outlines and Dimensions ]
- 10 -
HWE20150
GB
(
2-9/16
)
Unit : mm(in.)
-7/16
0
65
0 -10
(1
1-13/16)
(Actual length)
(Accessory)
Less than 700 (27-9/16)
Less than 300
Drain hose
(I.D
Ø
32 (1-1/4))
(4-7/16)(4-7/16)
P-Ø2.9
(1/8)
6
(1/4)
J
KL
K
J
KX (M-1)=N
11 (7/16)
112
112
Unit:mm(in.)
PEFY
-P54NMAU-E4
H
Model
PEFY
-P15,18NMAU-E4
PEFY
-P24,27,30NMAU-E4
PEFY
-P36,48NMAU-E4
P
N
JK
L
M
PEFY
-P06,08,12NMAU-E4
800
1000
1200
1500
1700
(31-1/2)
(39-3/8)
(47-1/4)
(59-1/16)
(66-15/16)
44
54
49
54
54
370
320
330
260
150
300
4
4
5
5
1480
1280
990
780
10
10
10
12
12
(1-3/4)
(2-3/16)
(1-15/16)
(2-3/16)
(2-3/16)
(14-5/8)
(12-5/8)
(13)
(10-1/4)
(5-15/16)
(1
1-13/16)
(30-3/4)
(39)
(50-7/16)
(58-5/16)
700
900
1100
1600
(27-9/16)
(35-7/16)
(43-5/16)
(63)
Q
(55-1/8)
1400
250
~350
500
~600
(2)
~(5-15/16)
(19-1
1/16)
~(23-5/8)
(15-3/4)
~(19-1
1/16)
400
~500
50
~150
150
~250
(5-15/16)
~(9-7/8)
R
1500
1700
2200
(51-3/16)
(59-1/16)
(66-15/16)
(78-3/4)
2000
1300
(86-5/8)
S
(9-7/8)
~(13-13/16)
(1
1-13/16)
Min. 300mm
(3-15/16~
7-7/8)
(17-3/4)
(1
1-13/16)
50
(2)
700
(27-9/16)
50
(2)
700
(27-9/16)
(17-3/4)
Supply
air
Supply
air
Intake air
Intake air
(17-3/4X17-3/4)
Access door 1
(450×450)
475
(18-3/4)
450
Min. 300mm
450
Q
Control box
Control box
Fig.4
Fig.5
Access door 3
Access door 4
Q
50 (2)
777
(30-5/8)
50 (2)
777
(30-5/8)
H
100~
200
S
Maintenance access space
Maintenance access space
Bottom of indoor unit
Bottom of indoor unit
(V
iewed from the direction
of the arrow
B
)
(V
iewed from the direction
of the arrow
B
)
Intake air
(7/16)
(13/16)
Supply air
Min. 10mm
Min. 20mm
Access door 3
Ceiling
B
Fig.3
Ceiling beam
Control box
(7/16)
Intake air
Supply air
(11-13/16)
(17-3/4X17-3/4)
(1
1-13/16)
(17-3/4)
(17-3/4)
(17-3/4)
(17-3/4)
(2
~
5-15/16)
Bottom of indoor unit
(17-3/4X17-3/4)
(V
iewed from the direction
of the arrow
A)
(3-15/16~7-7/8)
Intake air
Supply air
Fig.2
Fig.1
A
Min. 10mm
Min. 300mm
Control box
Access door 2
(450×450)
Ceiling
Ceiling beam
475
(18-3/4)
450
700
(27-9/16)
Min. 300mm
450
100~
200
Q
450
R
50
~
150
450
Maintenance access space
Access door 1
(450×450)
(17-3/4X17-3/4)
Access door 2
(450×450)
Control box
(1)
When a space of 300mm or more is available below the unit between the unit and the ceiling. (Fig.1)
•
Create access door 1 and 2 (450x450mm each) as shown in Fig.2.
(Access door 2 is not required if enough space is available below the unit for a maintenance worker to work in.)
(2)
When a space of less than 300mm is available below the unit between the unit and the ceiling.
(At least 20mm of space should be left below the unit as shown in Fig.3.)
•
Create access door 1 diagonally below the control box and access door 3 below the unit as shown in Fig.4.
or
•
Create access door 4 below the control box and the unit as shown in Fig.5.
Secure enough access space to allow for the maintenance, inspection, and replacement of the motor
, fan, drain pump, heat exchan
ger
,
and control box in one of the following ways.
Select an installation site for the indoor unit so that it's maintenance access space will not be obstructed by beams or other
objects.
[Maintenance access space]