Item
Model
Power source
Btu/h
Cooling capacity*
1
/ Heating capacity*
1
kW
Height
mm[in]
Dimension Width
mm[in]
Depth
mm[in]
Net weight
kg[lb]
Airflow rate(Low-Mid-High)
CFM
Fan
in.WG
External staticpressure*
2
[Pa]
Sound level(Low-Mid-High)*
2
*
3
dB(A)
Filter
208, 230V 60Hz
P36NMAU-E
36,000/40,000
10.6/11.7
812-989-1,165
33-38-42
P48NMAU-E
48,000/54,000
14.1/15.8
989-1,201-1,412
37-41-45
250[9-13/16]
732[28-13/16]
0.14-0.20-0.28-0.40-0.60
[35/50/70/100/150]
42[93]
Standard filter
Notes: *1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 80 °F (26.7 °C) D.B./67 °F (19.4 °C) W.B.
Outdoor: 95 °F (35 °C) D.B.
Heating: Indoor: 70 °F (21.1 °C) D.B.
Outdoor: 47 °F (8.3 °C) D.B./43 °F (6.1 °C) W.B.
Pipe length: 7.5 m (24-9/16 ft)
Height difference: 0 m (0 ft)
*2 The external static pressure is set to 0.20 in. WG (50 Pa) at factory shipment.
*3 The operating noise is the data that was obtained in an anechoic room.
P54NMAU-E
54,000/60,000
15.8/17.6
1,600[63]
46[102]
1,042-1,254-1,483
39-43-48
1,400[55-1/8]
KB79P490H01_GB_e.p65