8.4. Dipswitch setting
8.4.1. Discharge Air Control (Factory Setting)
8.3.
Dipswitch setting
1.
Discharge Air Control (Factory Setting)
(1) SW1 - Function Setting
Switch
Position
Function
Switch Setting
ON
OFF
1
Return Air Sensing
Location
Remote Controller
TH21
2
TH24 Temperature
Offset
a = 0 °F
ON
OFF
2
3
a = 1 °F
ON
OFF
2
3
a = 2 °F
ON
OFF
2
3
a = 3 °F
ON
OFF
2
3
3
4
Not Available
N/A
N/A
5
Remote display
Thermostat ON signal
Fan Output
6
Not Available
N/A
N/A
7
Not Available
N/A
N/A
8
Not Available
N/A
N/A
9
Auto restart after
power failure
Enabled
Disabled
10
Power start/stop
Enabled
Disabled
Factory Setting in Gray
Dip switch settings must be made while the unit is stopped. There is no need to power cycle the unit.
(2) SW3 - Function Setting
Switch
Position
Function
Switch Setting
ON
OFF
1
Heat Pump or
Cooling Only
Cooling Only
Heat Pump
2
Not Available
N/A
N/A
3
Not Available
N/A
N/A
4
Fan Operation
During Defrost
ON During Defrost
OFF During Defrost
5
Not Available
N/A
N/A
6
Capacity Code Up
Capacity Code Up
Capacity Code not Up
7
Not Available
N/A
N/A
8
TH2
1
value for
Thermo ON/OFF in
Heating mode
TH2
1
Value for Thermo ON/OFF in Heating Mode
SW3-8
SW3-9
Thermo ON
Thermo OFF
OFF
OFF
68 °F [20 °C]
70 °F [21 °C]
ON
OFF
N/A
N/A
OFF
ON
48 °F [9 °C]
50 °F [10 °C]
ON
ON
57 °F [14 °C]
59 °F [15 °C]
9
10
Not Available
N/A
N/A
Factory Setting in Gray
Dip switch settings must be made while the unit is stopped. There is no need to power cycle the unit.
PAC-AH001-1
41