Control Type
Type 1 (For Temperature Control)
(SWA-2)
Type 2 (For Capacity Control)
(SWA-3)
Control
Relationship
(COOL)
Set point temperature = 5.625 X Ain
+ 40.775 [°F]
[Ain = Input Temperature]
Set point temperature = -5.625 X Ain
+ 100.4 [°F]
[Ain = Input Temperature]
Input Voltage
Setting Temperature
Input Voltage
Setting Temperature
NOTE
COOL operation mode must be set using City Multi controller
Cooling Set-point Range with 3rd Party Controller
• Discharge Air Control: 46.4~82.4 °F [8~28 °C]
PAC-AH001-1
Specifications are subject to change without notice.
20