7.1.4. Float switch control
[
VII
Microprocessor Control ]
- 13 -
HWE13010
GB
In the air : Detected that the float switch is OFF for 15 seconds.
2. Dry operation
1. Termoregulating function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
Dry thermo ON Room temperature desired tempe 2°F
Dry thermo OFF Room temperature desired temperature
(2) Frozen prevention control
No control function
2. Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display DRY.
3. Press the [Set Temperature] button to set the desired tempera-
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Dry 67 to 87°F
Room temperature
3 min. passed since starting operation
Dry thermo
ON time (min)
Dry thermo
OFF time (min)
Thermo regulating signal
Room temperature (T1)
Over 64°F
ON
T1
83°F
9
3
83°F > T1 79°F
7
3
79°F > T1 75°F
5
3
75°F > T1
3
3
OFF
Unconditional
3
10
Less than 64°F
Dry thermo OFF
Dry thermo
Fan speed notch
ON
[Low]
OFF
Excluding the following
Stop
Room temp. < 64°F
[Low]
ON
OFF
15sec.
15sec.
15sec. 1min.30sec.
1min.30sec.
Float SW
In the water
In the air
In the water
Error
postponement
Drain pump
abnormal
PAR-21MAAU
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
7.2. Dry Operation
7.2. Dry Operation
Dry Operation
(Available Control Modes)
Control Mode
Return Air Control
Discharge Air Control
Controller
Type
City Multi Controller
●
*1
3
rd
Party
Controls
Type 1
*1
*1
Type 2
*1
*1
*1 Dry mode only available when using City Multi Controller set to Return Air Control
1.) How to operate
1) Press POWER ON/OFF button.
2) Press the operation MODE button to display DRY.
3) Press the TEMP. button to set the desired temperature.
Note:
The set temperature changes 2 °F when the TEMP. button is pressed one
time.
Dry Set-point Range
•
Return Air Control: 67~87 °F [19~31 °C]
2.) Thermo regulating function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
•
Room temperature ≥ desired tempe 2° F ···Dry Thermo ON
•
Room temperature < desired temperature ···Dry Thermo OFF
Room
temperature
3 min. passed since starting operation
Dry thermo
ON time (min)
Dry thermo
OFF time (min)
Thermo regulating
signal
Room temperature
(TH21)
Over 64 °F
ON
T1 ≥ 83°F
9
3
83°F > T1 ≥ 79°F
7
3
79°F > T1 ≥ 75°F
5
3
75°F > T1
3
3
OFF
Unconditional
3
10
Less than 64°F
DRY thermo OFF
(2) Frozen prevention control
•
No control function
3.) Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
Dry thermo
Fan speed notch
ON
[Low]
OFF
Room temp. ≥ 64°F
Stop
Room temp. < 64°F
[Low]
7.2.1. How to operate
(1) Using CITY MULTI Controller
.
1. Press POWER
ON/OFF
button.
2. Press the operation
MODE
button to display DRY.
3. Press the
TEMP.
button to set the desired temperature.
NOTE
The set temperature changes 2 °F when
the
TEMP.
button is pressed one time.
Dry Set-point Range
• Return Air Control: 67~87 °F [19~31 °C]
7.2.2. Thermo-regulating function
(1) Thermo-regulating function (Function to prevent restarting for 3 minutes)
Control of Dry Thermo ON and Dry Thermo OFF by the thermo regulating signal and the room temperature
(TH21).
• Room temperature ≥ desired tempe 2° F ∙∙∙Dry Thermo ON
• Room temperature < desired temperature ∙∙∙Dry Thermo OFF
PAC-AH001-1
Specifications are subject to change without notice.
22