2. M-NET control
DATA U5
SYSTEM DESIGN
Syste
m H
2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7 side, Booster for long M-NET wiring
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
2. Address should be set to Indoor units, LOSSNAY and central controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to
2-3 "System configuration
restrictions".
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
Indoor unit
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
*1
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For G-50A, 12V DC should be used with the PAC-SC50KUA. For AG-150A, 24V DC should be used with the PAC-SC51KUA.
*1
01
02
03
30
TB15
TB5
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA
TB5
TB15
TB15
TB3
TB15
MA R/C
(Main)
(Sub)
MA R/C
TB15
Indoor unit
MA R/C
SRU
Wireless R/C
*1
*1
41
45
46
TB15
TB5
TB5
TB5
TB15
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
000 or 201
PSU
Power supply
unit (PSU)
(PAC-SC51KUA)*2
SC*3
203
SC*3
Group 2
Group 1
Group 21
Group 31
Group 34
Group 35
ME R/C
PZ-52SF
142
143
42
43
TB5
LOSSNAY
TB5
Group 33
Group 32
TB3
TB7
TB7
TB7
TB7
TB7
TB3
52
51
OC
OS
PUHY-HP-TSHMU
TB3
TB3
92
91
OC
OS
PUHY-HP-TSHMU
TB3
97
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
PUHY-HP-THMU
4 - 83