3. Piping Design
DATA U5
SYSTEM DESIGN
System H
Table3-2-2-4. R410A Joint selection rule
Total down-stream Indoor capacity
Joint
~ P72
CMY-Y102S-G2
P73
~ P144
CMY-Y102L-G2
P145 ~ P234
CMY-Y202-G2
*First Joint is always CMY-Y202-G2;
*Concerning detailed usage of Joint parts, refer to its Installation Manual.
Outdoor Twinning Kit
CMY-Y100VBK2
Note1. No Joint after Header; Piping direct to Indoor Unit from Header;
Note2. If the A/C system is designed to use cooling-mode under outside temperature 10°C [50°F], H’<=40m [131ft].
Note3. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length=Actual piping "M" x Quantity of bent.
H (OU above IU)
h1
H' (OU under IU)
h2
1st Joint
Joint
b
a
L2
L1
IU
IU
IU
IU
g
IU
e
IU
d
C
D
IU
f
E
T
S
A
B
Header
Capped
IU : Indoor unit , OU : Outdoor unit
Fig. 3-2-1B Piping scheme
c
2m [6.56ft]
To indoor unit
To indoor unit
To indoor unit
To indoor unit
2m [6.56ft] max
Trap (gas
pipe only)
Upward
incline
Downward
incline
Install the pipes from the outdoor unit to the branch
joint with a downward incline.
If the length of pipe between the branch joint and outdoor
unit exceeds 2m [6.56ft], provide at rap at a distance 2m [6.56ft] or
less from the branch joint.
OK
NO
3-2-2. PUHY-HP144-192TSHMU Piping
Table3-2-2-1. Piping length
(m [ft.])
Item
Piping in the figure
Max. length Max. equivalent length
Total piping length
S+T+A+B+C+D+E+a+b+c+d+e+f+g
300 [984']
-
Distance between OU and OU
S+T
10[32']
-
Height between OU and OU
h2
0.1[0.3']
-
Farthest IU from OU (L1)
S(T)+A+C+D+E+g / S(T)+A+B+c 150 [492']
175 [574']
Farthest IU from the first Joint (L2)
C+D+E+g / B+c
40 [131']
40 [131']
Height between OU and IU (OU above IU) H
50 [164']
-
Height between OU and IU (OU under IU) H'
40 [131']
-
Height between IU and IU
h1
15 [49']
-
OU: Outdoor Unit, IU: Indoor Unit
Table3-2-2-3. Piping "A" size selection rule (mm [in.])
Outdoor and the first Joint
Pipe(Liquid)
Pipe(Gas)
CMY-Y100VBK2=CMY-Y202-G2
ø15.88[5/8"]
ø28.58[1-1/8"]
For Piping size "S","T", please refer to specification of the Twining kit CMY-Y100VBK2 at the Outdoor unit's
external drawing.
Table3-2-2-2. Bent equivalent length "M"
Outdoor Model
M (m/bends [ft./bends])
PUHY-HP144TSHMU
0.50
[1.64]
PUHY-HP192TSHMU
0.50
[1.64]
OU
OU