1. For hanging from the ceiling [Fig. 2.2.1] (P.2)
•
Provide an inspection hole 450 mm square in the ceiling surface as shown in
[Fig. 2.3.1] (P.2).
•
Install the unit in a suitable location (such as in the ceiling of a corridor or in the
bathroom etc) away from places regularly occupied. Avoid installing in the center
of a room.
•
Ensure a pull out strength of at least 60 kg per bolt for hanging bolts.
•
Be sure to install the BC controller horizontally.
Warning:
Be sure to install the unit in a place that can sustain the entire weight.
If there is a lack of strength, it may cause the unit to fall down, resulting in an
injury.
Caution:
Be sure to install the unit horizontally.
2.3. Securing installation and service space
1. For hanging from the ceiling
(This is a reference view showing the least installation space.)
[Fig. 2.3.1] (P.2)
<A> Top view
<B> Front view
A
Inspection hole
B
On the side of outdoor unit piping
C
Control box
D
On the side of indoor unit piping
*1 Dimensions with which pipe connection can be handled at site
Notes:
*1 Refer to “Restrictions on piping length” on P. 4.
*2 Please refer to the figure “Distance between BC controller and farthest
Indoor unit” when the distance between BC controller and farthest in-
door unit exceeds 40 m. (Not applicable to the P250 model indoor unit)
*3 The values in the parentheses show the maximum piping length to be
followed when the connection capacity of the indoor unit is 200 or more.
*4 In the system to which indoor units of the P200 model or above are con-
nected, neither a branch joint nor a branch header may be used.
*5 Do not connect the P200 or P250 models of indoor units and other mod-
els of indoor units at the same port.
*6 In the system to which indoor units of the P100 through P140 models are
connected, merge the two ports before connecting them. (Set DIP SW4-6
on the BC controller to ON.)
*7 It is possible to connect the P100 through P140 models of indoor units to
a single port. (Set DIP SW4-6 to OFF.) Note that the cooling capacity will
somewhat decrease. (The factory setting for DIP SW4-6 is OFF.)
*8 Indoor units that are connected to the same branch joint cannot be simul-
taneously operated in different operation modes.
Model name
A
B
CMB-P104V-G1
CMB-P105V-G1
CMB-P106V-G1
648
CMB-P108V-G1
-
CMB-P1010V-G1
CMB-P1013V-G1
1098
CMB-P1016V-G1
CMB-P108V-GA1
CMB-P1010V-GA1
1110
200
CMB-P1013V-GA1
CMB-P1016V-GA1
CMB-P104V-GB1
648
-
CMB-P108V-GB1
CMB-P1016V-HA1
1110
200
CMB-P1016V-HB1
1098
-
Length
(Unit: m)
Item
Piping portion
Allowable value
A+B+a+b
Total piping length
+c+d+e
Longest piping length
A+e
Between outdoor unit and
A
Below 110
BC controller
Between indoor units and BC controller
e
Below 40 *2
Above outdoor unit
H
Below 50
Below outdoor unit
H1
Below 40
Between indoor units and BC controller
h1
Below 15
(Below 10)*3
Between indoor units
h2
Below 15
(Below 10)*3
Dif
ference of elevation
Between
indoor and
outdoor units
Not to exceed the
maximum refriger-
ant piping length *1
165 m or less
(Equivalent length
of 190 m or less)
2.4. Checking the installation site
Check that the difference of elevation between indoor and outdoor units and the
length of refrigerant piping are within the following limitations.
1. CMB-P104, 105, 106, 108, 1010, 1013, 1016G1 (In the case the outdoor unit
is 14-hp (P350 model) or less, and 16 or fewer ports are used.)
[Fig. 2.4.1] (P.2)
A
Outdoor unit
B
BC controller
C
Indoor unit
D
P100 - P250 model: 2 ports merged.
E
Less than H=50 m (when the outdoor unit is higher than the indoor unit)
F
Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
G
Twinning pipe (for Y Series) CMY-Y102S-G2
H
Combined pipe (CMY-R160-J1: optional)
I
Less than 110 m
J
Less than 40 m
K
Up to three units for 1 branch hole
Total capacity: less than 80 (but same in cooling/heating mode)
L
Less than h1=15 m (10 m or less for 200, 250 unit type)
M
Less than h2=15 m
Distance between BC controller
and farthest indoor unit
Height difference between
BC controller and farthest
indoor unit (m)
15
10
5
20
10
0
0
Distance between BC contoroller
and farthest indoor unit (m)
70
60
50
40
30
2. CMB-P108, 1010, 1013, 1016GA1, P104, 108GB1 (GA1: In the case the out-
door unit is 26-hp (P650 model) or less.)
CMB-P1016HA1, 1016HB1 (HA1: In the case the outdoor unit is 28-hp
(P700 model) or more.)
[Fig. 2.4.2] (P.3)
A
Outdoor unit
B
MAIN BC controller
C
SUB BC controller
D
Indoor unit
E
The twinning kit is connected inside the outdoor unit on the low-pressure side.
When outdoor units of different capacities are connected, connect the twinning
kit to the unit with a higher capacity.
F
Twinning pipe (for R2 series) CMY-R100VBK, CMY-R200VBK
(for WR2 series) CMY-Q100VBK
G
Twinning pipe (for Y series) CMY-Y202-G2, CMY-Y102L-G2, CMY-Y102S-G2
H
Twinning pipe (CMY-R160-J1: optional)
I
Twinning pipe (for Y series) CMY-Y102S-G2
J
P100 - P250 model: 2 ports merged
K
Maximum of 3 units per a pair of ports
Total capacity of 80 or below
All units connected to the same port must be in the same operation mode.
L
Less than H=50 m (when the outdoor unit is higher than the indoor unit)
M
Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
N
Less than h1=15 m (10 m or less for 200, 250 unit type)
O
Less than h2=15 m