![Mitsubishi Electric Citi Multi Series Technical & Service Manual Download Page 23](http://html.mh-extra.com/html/mitsubishi-electric/citi-multi-series/citi-multi-series_technical-and-service-manual_237995023.webp)
23
9
TROUBLESHOOTING
9-1. HOW TO CHECk THE PARTS
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 50 to 86
_
F)
Refer to “9-1-1. Thermistor”.
Room temperature
thermistor (TH21)
Liquid pipe thermistor
(TH22)
Gas pipe thermistor
(TH23)
Normal
4.3 to 9.6 k
"
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(Winding temperature 68°F)
Measure the resistance between the terminals using a tester.
Drain pump (DP) (Option)
i-see sensor
(Option)
Drain float switch (FS)
(Option)
1
3
YLW
YLW
Normal
Abnormal
290
"
Open or short
State of moving part
Abnormal
DOWN
Other than open
UP
Normal
Open
Short
Other than short
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 68 to 86°F)
Vane motor (MV)
i-see sensor motor (MT)
(Option)
Abnormal
Open or short
Red - Yellow
Red - Blue
Red - Orange
Red - White
Connector
Normal
300
"
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 68 to 86°F)
Abnormal
Open or short
Red - Yellow
Red - Blue
Red - Orange
Red - White
Connector
Normal
250
"
Disconnect the connector then measure the resistance valve with a tester.
Linear expansion
valve (LEV)
Abnormal
Open or short
Normal
200
"
i
10%
White-Red
Yellow-Brown
Orange-Red
Blue-Brown
Orange
Red
White
Blue
Brown
Yellow
M
Refer to “9-1-2. Linear
expansion valve”.
MV
MV
Normal
Abnormal
1.857–3.132 V DC
Other than the normal
0.939–1.506 V DC
2
(
−
)–
4
(+)
i-see sensor connector
i-see sensor (At the ambient temperature of 50 to 104°F)
NOTE
: Be careful when handling static electricity.
1
(+)–
2
(
−
)
Other than the normal
Do not disassemble corner panel with
i-see sensor.
Black plastic tape
Turn on the indoor unit with black plastic tape on the outside of the i-see sensor controller board.
With electricity being turned on, measure the power voltage between connectors with a tester.
The i-see sensor rotates, and pull out the connector of motor for the i-see sensor.
2
1
Moving part
4
3
Switch
Magnet
Moving
Part
4 3 2 1
4 3
1
BlueBlackPink Brown
2
Yellow
Blue
Red
Orange
White
Yellow
Blue
Red
Orange
White
PLFY-P08NBMU-E2 PLFY-P12NBMU-E2 PLFY-P15NBMU-E2 PLFY-P18NBMU-E2
PLFY-P24NBMU-E2 PLFY-P30NBMU-E2 PLFY-P36NBMU-E2
OCH579