20
Control modes
Control details
1-1. Determinating thermostatic control function
(Function to prevent restarting for 3 minutes)
•
Room temperature
[
desired temperature
−
2°F ···Thermo-ON
•
Room temperature
]
desired temperature ···Thermo-OFF
1. Thermostatic
control function
Remarks
2-1. Hot adjust mode
The fan controller becomes the hot adjuster mode for the following conditions.
1
When starting the HEAT operation
2
When the thermostat function changes from OFF to ON.
3
When release the HEAT defrosting operation
2. Fan
A: Hot adjust mode starts.
B: 5 minutes have passed since the condition A or the indoor liquid pipe
temperature turned 95°F or more.
C: 2 minutes have passed since the condition A. (Terminating the hot adjust mode)
A
C
B
[Extra Low]
[Low]
Set fan speed by the remote controller
Hot adjust mode *1
*1 "STAND BY"
will be displayed
during the hot
adjust mode.
Continue to the next page
By the remote controller setting (switch of 4 Auto)
When [Auto] is set, fan speed is changed depending on the value of:
Desired temperature - Room temperature
Give priority to under-mentioned controlled mode
2-1. Hot adjust mode
2-2. Preheating exclusion mode
2-3. Thermo OFF mode (When the compressor off by the thermostat)
2-4. Cool air prevention mode (Defrosting mode)
Type
Fan speed notch
[Low], [Med2], [Med1], [High], [Auto]
4 Auto type
8-4. HEAT OPERATION
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display HEAT.
3
Press the TEMP. button to set the desired temperature.
NOTE
: The set temperature changes 2°F when the or button is
pressed one time. Heating 63 to 83°F.
.
OCH579