Software
62
Mitsubishi Electric, MA00758A
Via External Memory Card
Transferring the system program to the operator panel via an external memory card
requires the following:
– File with new system program (OPSys_b*.cab).
– Compact Flash memory card (only in E1070, E1100, E1071, E1101 and E1151)
or USB Flash drive.
The transfer is made using the following steps:
1. Save the system program file (OPSys_b*.cab) in the root of the external Com-
pact Flash memory card or USB Flash drive.
2. Place the memory card in the operator panel, or connect the USB Flash drive,
and start the operator panel to update the system program automatically.
Downloading the System Program in E1012 and E1022
An Image Loader is used to download system programs to the operator panel via a
PC. The Image Loader is available from the website. The transfer is made via the se-
rial port using a CAB30 cable.
Updating of the system program to the operator panel requires the following:
– PC with Image Loader application.
– CAB30 cable.
Transfers Are Made in the Following Steps:
1. Run the Image Loader exe-file by double-clicking on it. Follow the instructions;
also described in the following steps:
2. Connect the cable between the PC and the operator panel.
3. Disconnect the power to the operator panel.
4. Set the panel in Image Load mode by setting mode switch number 2 in the ON
position according to the illustration below.
5. Reconnect power.
6. All operator panels connected to the COM-ports on the PC and currently set in
Image Load mode will be available for selection from a drop down list. Select
which operator panel to upgrade by selecting its MAC address (hex).
7. Click
Upgrade
.
8. When the upgrade is finished, disconnect power from the operator panel.
9. Change mode switch number 2 back in OFF position.
10.Reconnect power to the operator panel.
Note:
When updating an operator panel it is important to ensure that the power is not inter-
rupted during the transfer.
1 2 3 4
ON DIP