Hardware
Mitsubishi Electric, MA00758A
17
Technical Data
E1061
E1063
E1061 of
hardware
version type
no 07905 or
higher
E1063 of
hardware
version type
no 07915 or
higher
Front panel,
W x H x D
202 x 152 x 6 mm
Mounting depth
57 mm (157 mm including clearance) 57 mm (157 mm including
clearance)
Front panel seal
IP 66
Rear panel seal
IP 20
Touch screen material Touch screen: Polyester on glass, 1 million finger touch
operations.
Overlay: Autotex F157/F207.
Reverse side material Powder-coated aluminum
Weight
0.9 kg
Serial port RS422/
RS485
25-pin D-sub contact, chassis-mounted female with standard
locking screws 4-40 UNC.
Serial port RS232C
9-pin D-sub contact, male with standard locking screws 4-40 UNC.
Ethernet
Shielded RJ 45
USB
Host type A (USB 1.1), max output current 500 mA
Flash memory for
application
12 MB (incl. fonts)
Real time clock
±20 PPM + error because of ambient temperature and supply
voltage. Total maximum error: 1 min/month at 25
°
C
Temperature coefficient: 0.004 ppm/
°
C
2
Real time
clock battery
CR2450 (UL and cUL: Sanyo or Panasonic)
Minimum lifetime: 3 years
Power consumption
at rated voltage
Normal: 0.25 A
Maximum: 0.45 A
Normal: 0.2 A
Maximum: 0.4 A
Display
Transmissive
color STN-LCD.
320 x 240 pixels.
64K colors
Transmissive
monochrome
STN-LCD.
320 x 240 pixels
TFT-LCD.
320 x 240
pixels.
64K colors.
TFT-LCD.
320 x 240
pixels.
16 greyscales.
CCFL backlight
lifetime at the
ambient tempe-
rature of +25
°
C:
>75,000 h.
CCFL backlight
lifetime at the
ambient tempe-
rature of +25
°
C:
>58,000 h.
LED backlight lifetime at the
ambient temperature of
+25
°
C: >20,000 h.
Active area of
display, W x H
115.2 x 86.4 mm
Fuse
Internal DC fuse, 2.0 AT, 5 x 20 mm
Power supply
+24V DC (20 - 30V DC). Power supply connector.
CE: The power supply must conform with the requirements
according to IEC 60950 and IEC 61558-2-4.
UL and cUL: The power supply must conform with the
requirements for class II power supplies.
Ambient temperature Vertical installation: 0
°
to +50
°
C
Horizontal installation: 0
°
to +40
°
C
Storage temperature -20
°
to +70
°
C
Relative humidity
5 - 85 % non-condensed