E-31
Table 5.6.17
Harmonics 2 register
Address
Number
of bytes
Access
Register Name
Unit
RANGE
Dec.
Hex.
3072 0C00h
2
R
THD (total harmonics distortion) current in Phase 1 (I1)
0.1%
0 to 2000
(200%)
3073 0C01h
2
R
THD (total harmonics distortion) current in Phase 1 (I2)
3074 0C02h
2
R
THD (total harmonics distortion) current in Phase 1 (I3)
3075 0C03h
2
R
THD (total harmonics distortion) current in Pole N (IN)
3076 0C04h
2
R
3
rd
harmonics ratio current in Phase 1 (I1)
3077 0C05h
2
R
3
rd
harmonics ratio current in Phase 2 (I2)
3078 0C06h
2
R
3
rd
harmonics ratio current in Phase 3 (I3)
3079 0C07h
2
R
3
rd
harmonics ratio current in Pole N (IN)
3080 0C08h
2
R
5
th
harmonics ratio current in Phase 1 (I1)
3081 0C09h
2
R
5
th
harmonics ratio current in Phase 2 (I2)
3082 0C0Ah
2
R
5
th
harmonics ratio current in Phase 3 (I3)
3083 0C0Bh
2
R
5
th
harmonics ratio current in Pole N (IN)
3084 0C0Ch
2
R
7
th
harmonics ratio current in Phase 1 (I1)
3085 0C0Dh
2
R
7
th
harmonics ratio current in Phase 2 (I2)
3086 0C0Eh
2
R
7
th
harmonics ratio current in Phase 3 (I3)
3087 0C0Fh
2
R
7
th
harmonics ratio current in Pole N (IN)
3088 0C10h
2
R
9
th
harmonics ratio current in Phase 1 (I1)
3089 0C11h
2
R
9
th
harmonics ratio current in Phase 2 (I2)
3090 0C12h
2
R
9
th
harmonics ratio current in Phase 3 (I3)
3091 0C13h
2
R
9
th
harmonics ratio current in Pole N (IN)
3092 0C14h
2
R
11
th
harmonics ratio current in Phase 1 (I1)
3093 0C15h
2
R
11
th
harmonics ratio current in Phase 2 (I2)
3094 0C16h
2
R
11
th
harmonics ratio current in Phase 3 (I3)
3095 0C17h
2
R
11
th
harmonics ratio current in Pole N (IN)
3096 0C18h
2
R
13
th
harmonics ratio current in Phase 1 (I1)
3097 0C19h
2
R
13
th
harmonics ratio current in Phase 2 (I2)
3098 0C1Ah
2
R
13
th
harmonics ratio current in Phase 3 (I3)
3099 0C1Bh
2
R
13
th
harmonics ratio current in Pole N (IN)
3100 0C1Ch
2
R
15
th
harmonics ratio current in Phase 1 (I1)
3101 0C1Dh
2
R
15
th
harmonics ratio current in Phase 2 (I2)
3102 0C1Eh
2
R
15
th
harmonics ratio current in Phase 3 (I3)
3103 0C1Fh
2
R
15
th
harmonics ratio current in Pole N (IN)
3104 0C20h
2
R
17
th
harmonics ratio current in Phase 1 (I1)
3105 0C21h
2
R
17
th
harmonics ratio current in Phase 2 (I2)
3106 0C22h
2
R
17
th
harmonics ratio current in Phase 3 (I3)
3107 0C23h
2
R
17
th
harmonics ratio current in Pole N (IN)
3108 0C24h
2
R
19
th
harmonics ratio current in Phase 1 (I1)
3109 0C25h
2
R
19
th
harmonics ratio current in Phase 2 (I2)
3110 0C26h
2
R
19
th
harmonics ratio current in Phase 3 (I3)
3111 0C27h
2
R
19
th
harmonics ratio current in Pole N (IN)
*All above data can not be monitored without VT unit.