E-26
Table 5.6.12 analog measurement 1 register
Address
Number
of bytes
Access
Register Name
Unit
Range
Dec. Hex.
768 0300h
2
R
Instantaneous current in Phase 1 (I1) *1
*4
Refer to table 2.4
769 0301h
2
R
Instantaneous current in Phase 2 (I2) *1
770 0302h
2
R
Instantaneous current in Phase 3 (I3) *1
771 0303h
2
R
Instantaneous current in Pole N (IN) *1,2
772 0304h
2
R
Reserved
773 0305h
2
R
Demand current in Phase 1 (I1) *1
*4
774 0306h
2
R
Demand current in Phase 2 (I2) *1
775 0307h
2
R
Demand current in Phase 3 (I3) *1
776 0308h
2
R
Demand current in Pole N (IN) *1,2
777 0309h
2
R
Reserved
778 030Ah
2
R
Instantaneous voltage in Line 1-2 (V12)
V
779 030Bh
2
R
Instantaneous voltage in Line 2-3 (V23)
780 030Ch
2
R
Instantaneous voltage in Line 1-3 (V13)
781 030Dh
2
R
Reserved
782 030Eh
2
R
Instantaneous voltage in Phase 1-N (V1N) *2
V
783 030Fh
2
R
Instantaneous voltage in Phase 2-N (V2N) *2
784 0310h
2
R
Instantaneous voltage in Phase 3-N (V3N) *2
785 0311h
2
R
Reserved
786 0312h
2
R
Reserved
787 0313h
2
R
Reserved
788 0314h
2
R
Reserved
789 0315h
2
R
Instantaneous power Factor *6
0.1%
790 0316h
2
R
Instantaneous frequency
Hz
791 0317h
2
R
Reserved
792 0318h
2
R
Reserved
793 0319h
2
R
Reserved
794 031Ah
2
R
Instantaneous active power *6
*5
795 031Bh
2
R
Reserved
796 031Ch
2
R
Reserved
797 031Dh
2
R
Reserved
798 031Eh
2
R
Demand active power *6
*5
799 031Fh
2
R
Reserved
800 0320h
2
R
Reserved
801 0321h
2
R
Reserved
802 0322h
2
R
Instantaneous reactive power *6
*5
803 0323h
2
R
Reserved
804 0324h
2
R
Reserved
805 0325h
2
R
Reserved
806 0326h
2
R
Instantaneous apparent power
*5
807 0327h
2
R
Demand reactive power *6
*5
808 0328h
2
R
Demand apparent power
*5
809 0329h
2
R
Instantaneous earth leakage (Ig) *1,3
0.1A
810 032Ah
2
R
Demand earth leakage (Ig) *1,3
0.1A
811 032Bh
2
R
Fault current *8
*7
*1 Only data of current (from 300h to 308h) and earth leakage (032Ah, 032Bh) can be monitored without VT unit.
*2 In case of 3φ3W, N Pole measurements ( 303h, 308h, 30Eh to 310h) can not be monitored.
*3 Earth leakage (32Ah, 32Bh) can not be monitored without E1 module.
*4 *1 In case of “In=250 to 315”, Unit: 0.1A. In case of “In=500 to 6300”, Unit: 1A.
*5 In case of “In=250 to 630”, Unit: 0.1kW, 0.1kvar, 0.1kVA. In case of “In=1000 to 6300”, Unit: 1kW, 1kvar, 1kVA.
*6 Minus data is expressed as two's complement.
*7 In case of “LTD, STD, INST”, Unit: 10A. In case of “GFR”, Unit: 1A. In case of “ER”, Unit: 0.1A.
Fault cause can be monitored with Alarm and trip information (0252h).
*8 In case of “UVT”, Data: non (0).