MITSUBISHI ELECTRIC 9900CX SERIES UPS
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-1
3.0 INSTALLATION AND OPERATION
3.1 TRANSPORTATION AND INSTALLATION
Table 3.1
How to transport and install the system
Transportation
Installation
Transport unit with forklift.
Using the pre-drilled 2 or 4 holes in the each UPS
channel base*, anchor the unit using appropriate
hardware. (Not provided)
* 4x 4-holes bases and 3x 2-holes bases
CAUTION :
Do not transport in a horizontal position. Cabinets must be
maintained upright /- 15
°
of the vertical during handling.
CAUTION : Floor shall be flat and level. 3 inches surrounding mounting holes
shall be flush with maintenance pad or floor.
3.2 INSTALLATION PROCEDURE
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights.
Table 3.2
List of UPS Weights
UPS Capacity (kVA)
1050
1400
1750
2100
Weight (lb.)
6283
9580
11770
13530
B) Minimum clearance required for ventilation
Right side
25 mm (1 inch) (not required when sidecars are used)
Left side
25 mm (1 inch) (not required when sidecars are used)
Back side
0.0 mm (0 inch)
Top side
600 mm (24 inches) (for air flow)
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
1000 mm (39 inches)
Sides
0.0 mm (0 inch)
Back side
0.0 mm (0 inch)
Top side
500 mm (20 inches)