MITSUBISHI ELECTRIC 9900CX SERIES UPS
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-17
Table 1.6
Rating of Contactors, Breaker and Fuses
IDENTIFI-
CATION
APPLICATION
OUTPUT CAPACITY OF EQUIPMENT
1050kVA 1400kVA 1750kVA
2100kVA
1000kW
1330kW
1660kW
2000kW
Conta
c
to
rs
CB1
AC input contactor
452A
CB2P,CB2N Battery
contactor
285A
CB3 STS
contactor
452A
(6.6kA for 3 sec
)
704A
(12kA for 3 sec
)
52C
Inverter output contactor
452A
52S Bypass
contactor
1278A 1992A
2843A
88RC
Control circuit contactor
20A
Br
eak
er
s
User supply
Battery disconnect breaker
(Recommended)
3000A 4000A 5000A 6000A
User supply
AC input breaker
(Recommended)
1600A 2500A 3000A 4000A
User supply
Bypass input breaker
(Recommended)
1600A 2500A 3000A 4000A
FP, FC, FN
DC fuse
315A / 690V
FBP, FBN
DC fuse
1000A / 690V
FBR1, FBR2, FBR3
FBR, FBS, FBT
FBO1, FBO2, FBO3
Control power fuse
12A / 600V
FOA, FOB, FOC
FIA, FIB
FUA, FUB, FUC
Control power fuse
12A / 600V
(OPTION)
FSU, FSV, FSW
Bypass input fuse
2000A /
500V
2800A /
650V
3600A / 550V
(OPTION)
FDU, FDV, FDW
Parallel control
circuit fuse (optional)
3A / 600V
* Rating would be changed.