(4) List of automatically-set parameters
The following tables show which parameters are changed in each of the automatic parameter settings.
⋅
Normal PID setting
When the PID display increments are not extended
* In this setting, the dedicated parameter list is not displayed while FR-PU07-01 is connected. (However, when another setting is made to activate the PID
control, the list may be displayed according to the setting. (
Refer to page 319 for the details.
)
⋅
Extended PID display increment setting
When the PID display increments are extended
*
Pr. 934
and
Pr. 935
settings affect displays of other parameters. Perform automatic setting of the extended PID display increments first. By doing this, the
dedicated parameter list will be displayed when FR-PU07-01 is connected. In the initial status, the
Pr. 999
setting is applied for the display. After the setting, the
Pr. 934
and
Pr. 935
settings are applied.
The 3-line monitor is displayed first after the automatic setting while a parameter unit (FR-PU07(-01)) is connected.
⋅
GOT initial setting (PU connector) (
Pr. 999
= "10")
CAUTION
⋅
If the automatic setting is performed with
Pr. 999
or the parameter setting mode, the listed settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the listed parameters will not cause any problem.
Parameter
Name
Initial
value
Automatically set to
Refer to page
759
PID unit selection
9999
9999
774
PU/DU monitor selection 1
9999
9999
775
PU/DU monitor selection 2
9999
9999
776
PU/DU monitor selection 3
9999
9999
934
PID display bias coefficient
9999
9999
935
PID display gain coefficient
9999
9999
Parameter
Name
Initial
value
Automatically set to
Refer to page
759
PID unit selection
9999
4
774
PU/DU monitor selection 1
9999
52
775
PU/DU monitor selection 2
9999
53
776
PU/DU monitor selection 3
9999
54
934
PID display bias coefficient
9999
0
935
PID display gain coefficient
9999
100
—
3-line monitor start setting
9999
The 3-line monitor is displayed
first.
Parameter
Name
Initial
value
Automatically set to
Refer to page
79
Operation mode selection
0
1
118
PU communication speed
192
192
119
PU communication stop bit length
1
10
120
PU communication parity check
2
1
121
Number of PU communication retries
1
9999
122
PU communication check time interval
9999
9999
123
PU communication waiting time setting
9999
0ms
124
PU communication CR/LF selection
1
1
340
Communication startup mode selection
0
0
REMARKS
Always perform an inverter reset after the initial setting.