214
Communication operation and setting
4.19.3 Initial settings and specifications of RS-485 communication
(Pr. 117 to Pr. 124, Pr. 331 to Pr. 337, Pr. 341, Pr. 549)
[PU connector communication related parameter]
Used to perform required settings for communication between the inverter and personal computer.
There are two different communications: communication using the PU connector of the inverter and
communication using the RS-485 terminals.
You can perform parameter setting, monitor, etc. using the Mitsubishi inverter protocol (computer link
communication), Modbus-RTU protocol and BACnet MS/TP protocol.
To make communication between the personal computer and inverter, initialization of the communication
specifications must be made to the inverter.
Data communication cannot be made if the initial settings are not made or there is any setting error.
Parameter
Number
Name
Initial Value
Setting Range
Description
117
PU communication station
number
0
0 to 31
Specifies the inverter station number.
Set the inverter station numbers when two or
more inverters are connected to one personal
computer.
118
PU communication speed
192
48, 96, 192, 384
Set the communication speed.
The setting value
×
100 equals the
communication speed.
For example, the communication speed is
19200bps when the setting value is "192".
119
PU communication stop bit
length
1
Stop bit length
Data length
0
1bit
8bit
1
2bit
10
1bit
7bit
11
2bit
120
PU communication parity
check
2
0
Without parity check
1
With odd parity check
2
With even parity check
121
Number of PU
communication retries
1
0 to 10
Set the permissible number of retries at
occurrence of a data receive error. If the
number of consecutive errors exceeds the
permissible value, the inverter trips.
9999
If a communication error occurs, the inverter
will not come to trip.
122
PU communication check
time interval
9999
0
No PU connector communication
0.1 to 999.8s
Set the interval of communication check time.
If a no-communication state persists for
longer than the permissible time, the inverter
trips.
9999
No communication check
123
PU communication waiting
time setting
9999
0 to 150ms
Set the waiting time between data
transmission to the inverter and response.
9999
Set with communication data.
124
PU communication CR/LF
selection
1
0
Without CR/LF
1
With CR
2
With CR/LF
The above parameters can be set when
Pr. 160 User group read selection
= "0".
Summary of Contents for 700 Series
Page 11: ...MEMO ...
Page 23: ...12 MEMO ...
Page 341: ...330 MEMO ...
Page 365: ...354 MEMO ...
Page 379: ...368 MEMO ...
Page 397: ...386 MEMO ...
Page 414: ...403 MEMO ...