1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
iii
MITSUBISHI ELECTRIC 1100 SERIES UPS
LIST OF FIGURES
Figure 1.1 Single Line Diagram - Normal Operation: Load powered by UPS inverter ........... 1-10
Figure 1.2 Single Line Diagram - Bypass Operation: Load fed through static bypass line. ... 1-11
Figure 1.3 Single Line Diagram - Battery Operation .............................................................. 1-12
Figure 1.4 UPS Parts Location (10, 20kVA only) --- Battery Built-in Cabinet model ........ 1-13
Figure 1.5 UPS Parts Location (10, 20, 30, 40, 50kVA) --- Standard Cabinet model ....... 1-14
Figure 1.6 UPS Parts Location (Bypass Module) .................................................................. 1-15
Figure 1.7 External I/F Module .............................................................................................. 1-15
Figure 2.1 Operation/Display Panel (Front panel) ................................................................... 2-1
Figure 2.2 Main screen ........................................................................................................... 2-2
Figure 2.3 Startup guidance .................................................................................................... 2-2
Figure 2.4 Shutdown guidance ............................................................................................... 2-2
Figure 2.5 Screen select menu ............................................................................................... 2-2
Figure 2.6 Input values ............................................................................................................ 2-3
Figure 2.7 Output values ......................................................................................................... 2-3
Figure 2.8 Measurement during .............................................................................................. 2-3
Figure 2.9 Each Power Converter Module .............................................................................. 2-3
Figure 2.10 Status log ............................................................................................................. 2-3
Figure 2.11 Battery log ............................................................................................................ 2-3
Figure 2.12 Power Converter Failure log ................................................................................ 2-3
Figure 2.13 Power C onverter Failure log ............................................................................... 2-3
Figure 2.14 Remote/Local operation select ............................................................................. 2-4
Figure 2.15 Date & Time adjustment....................................................................................... 2-4
Figure 2.16 Main screen ......................................................................................................... 2-4
Figure 2.17 Measurement screen ........................................................................................... 2-4
Figure 2.18 Main screen (Fault indication) .............................................................................. 2-5
Figure 2.19 Message screen ................................................................................................... 2-5
Figure 2.20 MENU Tree .......................................................................................................... 2-6
Figure 2.21 External Signal Terminal Block (NEC Class2) ..................................................... 2-8
Figure 2.22 External Signal Terminal Block (NEC Class2) ..................................................... 2-9
Figure 2.23 Control Wiring for External Contacts .................................................................. 2-10
Figure 2.24 Remote "Start" Contact Connections ................................................................. 2-11
Figure 2.25 External communication connector (NEC Class2) ............................................. 2-12
Figure 3.1 UPS Components .................................................................................................. 3-1
Figure 3.2 Handling ................................................................................................................. 3-3
Figure 3.3 Clearance for ventilation and maintenance ............................................................ 3-4
Figure 3.4 Rear Clearance for ventilation and maintenance for
Battery Built-in Cabinet Model
...... 3-5
Figure 3.5 Install Power Converter Module and Bypass Module ............................................. 3-7
Figure 3.6 Hardware configuration .......................................................................................... 3-9
Figure 3.7 UPS Terminal Designation Battery Built-in Cabinet model (10kVA, 20kVA UPS)
.......................................................................................................................................... 3-10
Figure 3.8 UPS Terminal Designation Standard Cabinet model ......................................... 3-10
Figure 3.9 Input/Output Power Terminals ............................................................................. 3-11