1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-19
MITSUBISHI ELECTRIC 1100 SERIES UPS
Table 1.6
Rating of Contactors and Fuses
Component
Description
Component Rating @ 208V, 3-phase, 60 Hz
UPS Rating (kVA)
10
20
30
40
50
CB3
Static Bypass Input
Contactor
80A 80A 80A 80A 80A
52S
Static Bypass Contactor
150A
150A
150A
150A
150A
F6,F7,F8
AC Input Fuse
660V / 60A
F4,F5
Battery Input Fuse
660V / 60A
F9,F10,F11 AC Output Fuse
660V / 60A
F2,F3
Control Power
250V / 2A
F1
Control Power
500V / 5A
Internal Battery Input Fuse
500V / 150A