– 20 –

Self diagnosis function

We are constantly trying to do better service to our customers by installing such judges that show abnormality of each function as follows:

Outdoor heat exchanger fluid pipe
sensor error

Outdoor temperature sensor error

Broken outdoor sensor wire, poor connector connection

Description of trouble

Room temperature sensor error

Cause

Broken heat exchanger sensor (1) wire, poorconnector

connection

Disconnected sensor

Indoor fan motor error

Heat exchanger sensor (1) error

2 time flash

5 time flash

TIMER lamp ON

1 time flash

RUN lamp

2 time flash

1 time flash

TIMER lamp

RUN lamp keeps flashing

Broken room temperature sensor wire, poor connector connection

Defective fan motor, poor connector connection

Broken heat exchanger fluid pipe sensor wire, poor connector

connection

Characteristics of HEAT mode operation

   Mechanism and capacity of HEAT mode operation

Mechanism

The unit draws in heat from the cold outside air, transfers it indoors and heats the room. The heating capacity of the heat pump mechanism decreases
when the outside air temperature gets colder.

The hot air circulation system takes a while before warming up the room temperature.

If the outside temperature becomes extremely low, it would be better to use an additional source of heating.

   Defrosting

If the outside temperature becomes low and humidity is high, the heat exchanger in the outdoor unit may frost over, which prevents efficient heating.

If this happens, the automatic defroster is activated and during defrosting the heating operation stops for 5 to 10 minutes.

Both indoor and outdoor fans stop and the RUN light (green) blinks slowly (1.5 sec. ON, 0.5 sec. OFF) during defrosting.

The outdoor unit may give off some steam during defrosting. This is to help the defrosting process and is not a defect.

The HEAT operation resumes as soon as defrosting has been completed.

2 time flash

RUN lamp 2 time flash

Rotor lock

Defective compressor

Open phase on compressor

Defective outdoor unit boards

If heating operation is performed when the outside temperature is high, room temperature may become higher than the set temperature.

Trouble of outdoor unit

Over current

Compressor locking, open phase on compressor output,

shortcircuit on power transformer, closed control valve

Current cut

2 time flash

3 time flash

1 time flash

Over heat of power transistor

Over heat of compressor

4 time flash

5 time flash

RUN lamp ON

Broken power transformer, broken compressor wire

Broken discharge pipe sensor wire, poor connector connection

Compressor blockage

Overload operation, overcharge

Cooling problem

Gas shortage, defective discharge pipe sensor, closed control

valve

6 time flash

Error of signal transmission

Defective power supply, Broken signal wire, defective in/outdoor

unit boards

Discharge pipe sensor error

Broken discharge pipe sensor wire, poor connector connection

Suction pipe sensor error

Broken suction pipe sensor wire, poor connector connection

Broken power transistor sensor wire, poor connector connection

Power transistor sensor error

4 time flash

5 time flash

6 time flash

6 time flash

7 time flash

Heat exchanger sensor (2) error

Broken heat exchanger sensor (2) wire, poor connector
connection

Disconnected sensor

Closed service valve

Heat exchanger sensor (1) error

Closed service valve

Disconnected sensor

RWA012A226_En

03.8.27, 6:48 PM

20

Summary of Contents for SCM45ZD-S

Page 1: ...st em conformidade com a Directiva EMC 88 336 CEE e a Directiva LV 72 23 CEE EMC 88 396 LV 73 23 USER S MANUAL MITSUBISHI DAIYA ROOM AIR CONDITIONER RWA012A226 ENGLISH MANUEL DE L UTILISATEUR CLIMATIS...

Page 2: ...trol 7 AUTO mode operation procedure 8 Temperature adjustment during AUTO 8 COOL HEAT DRY mode operation procedure 9 Concerning high power operation 9 Concerning economy operation 9 Air flow direction...

Page 3: ...s should never be connected to a gas pipe municipal water pipe light ning conductor or telephone earth cable Incorrect installation of the earth cable may produce an electric shock Depending on the pl...

Page 4: ...ould cause an electric shock fire etc If you notice anything abnormal smell of burning etc stop the system turn off the power switch and consult your dealer Continued use of the system in abnormal cir...

Page 5: ...same position the next time Page 8 Automatic selection of operating mode The Auto mode automati cally selects the operation mode HEAT COOL or DRY depending on the room temperature when switched on Ad...

Page 6: ...se Drains water from the dehumidified air Left right air flow adjustment fin Page 10 Air outlet Air blows out of here Air filter Removes dust or dirt from the inlet air Page 15 Unit indication section...

Page 7: ...n and then close the grill When removing the suction grill for internal cleaning or others open the grill by 65 degrees and then pull it to this side In emergencies this button can be used for turning...

Page 8: ...tch for setting the clock Page 11 OFF TIMER button This button selects OFF TIMER operation Page 11 TEMPERATURE button This button sets the room temperature This button changes the present time and TIM...

Page 9: ...MER TIME ACL FAN SPEED ON MODE LO MED HI AUTO TIME OFF HI POWER ECONO AM WARM Press the button COOL Press the button 1 When a change in temperature is desired Press the or button If you don t want the...

Page 10: ...ing or heating The unit operates 1 5 C higher than the setting temperature for the weak wind capacity during cooling or 2 5 C lower than that during heating A message is displayed on the remote contro...

Page 11: ...ily when the remote control is not used Operation program OPERATION MODE AUTO FAN SPEED AUTO AIR FLOW AUTO Operation starts by pressing the ON OFF button it stops if you press the button again Unit ON...

Page 12: ...r conditioner is not operating aim the remote control at the air conditioner Press the ON OFF button Press the OFF TIMER button OFF TIMER indicator OFF is blinking Press the or button Each time the bu...

Page 13: ...he timer operations that consist of the combination of the timer being set at both on and off Once this has been set and operations started operations will commence and end at the same time every day...

Page 14: ...ration is started by ON TIMER Mechanism The room temperature is checked 60 minutes before the timer is at ON Depending on the tempera ture at that time the operation starts 5 to 60 minutes before the...

Page 15: ...frequently Clogged filters may block the air flow and cause less efficient operation Don t go near high temperature places such as an electric carpet or stove Adjust the airflow direction properly Ad...

Page 16: ...sides as shown at right and insert securely Operating without putting back the air filters will make the unit dusty and may cause damage At the end of the season Stop the unit and turn off the power s...

Page 17: ...he air filters 2 Remove the filter holders with the natural enzyme filter and the photocatalytic washable deodorizing filter installed in the holders from the air conditioner 3 Remove the natural enzy...

Page 18: ...e than one air conditioner unit is being used Refrigerant oil recovery operation If the all of the indoor units are not operated at the same time for an extended period the cooling or heating performa...

Page 19: ...caused by refrigerating liquid moving within the unit You hear a slight cracking sound This is caused by heat expansion or contraction Remote control signals may not be received if the signal receiver...

Page 20: ...de of this range may result in the protection devices being activated preventing the unit from working Cooling operation Heating operation Outside temperature Approximately 21 to 43 C Below approximat...

Page 21: ...o 10 minutes Both indoor and outdoor fans stop and the RUN light green blinks slowly 1 5 sec ON 0 5 sec OFF during defrosting The outdoor unit may give off some steam during defrosting This is to help...

Page 22: ...en 45 Bedienungs und Anzeigenteil f r die Fernbedienung 47 AUTO Betrieb 48 Temperatureinstellung bei AUTO 48 COOL HEAT DRY Betrieb 49 Z r Betriebsart HI POWER 49 Z r Betriebsart ECONOMY 49 Einstellung...

Page 23: ...nn elektrischen Schlag verursachen Je nach Installationsstelle kann ein Stromunterbrecher not wendig sein Ohne einen Stromunterbrecher kann ein Elektroschock versursacht werden Nicht in der N he von S...

Page 24: ...uer usw verursachen Sobald Sie irgendetwas Au ergew hnli ches feststellen Geruch Brand usw das System stoppen Strom abschalten und Ih ren Lieferanten benachrichtigen Fortsetzung des Betriebes unter ab...

Page 25: ...chsten Start eingestellt Seite 48 Automatische Betriebswahl Der Betrieb Auto w hlt au tomatisch die Betriebsart HEAT COOL oder DRY je nach Raum temperatur Einstellung Luftstr mung AUTO Seite 49 K hlun...

Page 26: ...f hrung des Wassers von entfeuchteter Luft Feinregel Luftstromregelung links rechts Seite 50 Luftaustritt Luftaustritt hier Luftfilter H lt Staub und Schmutz vom Innenger t zur ck Seite 55 Betriebsanz...

Page 27: ...nn ebenso leicht die Gittermitte andr cken Die Finger an den seitlichen Einbuchtungen einhaken und das Gitter nach vorne um etwa 60 Grad aufklappen ON OFF Schalter des Ger tes Die obere oder die unter...

Page 28: ...51 Taste AUSSCHALTTIMER Die Taste dient zum W hlen des Ausschalttimerbetriebs Seite 51 TEMPERATURE Taste Diese Taste stellt die Raumtemperatur ein Taste ANNULLIEREN Diese Taste dient zum Annullieren...

Page 29: ...AM WARM Taste bet tigen COOL Taste bet tigen 1 Wenn eine andere Temperatur gew nscht wird Taste oder bet tigen Wenn das Programm AUTO nicht gew nscht wird wech selt man nach Wunsch von AUTO auf HEAT D...

Page 30: ...e Temperatur ist bzw auf 2 5 C unter der normalen Heizregeltemperatur Die Anzeige erscheint auf der Fernbedienung Die Anzeige der Gebl sestufe bleibt aus ANMERKUNG ANMERKUNG Bei H chstleistung erfolgt...

Page 31: ...m Luftstrom am Schlu einige Stunden lang nicht arbeiten lassen da sich sonst am Ausgangsgitter Kondenswasser bilden und herabtropfen kann Klappe nicht mit der Hand verstellen da sich der Kontrollwinke...

Page 32: ...um 22 30 ausschaltet Wenn die Klimaanlage nicht arbeitet die Fernbedienung an der Klimaanlage ausrichten Die Taste ON OFF EIN AUS dr cken Die Taste AUSSCHALTTIMER dr cken Die Anzeige OFF des AUSSCHAL...

Page 33: ...R Licht an Freigabeverfahren Zum Ausschalten der Timeranzeige die Taste ANNULLIEREN dr cken 3 Betrieb des Programm TIMERS Die Timerbetriebsarten die aus einer Kombination der Timereinstellungen einges...

Page 34: ...ert Je nach der dann herrschenden Tempera tur beginnt der Betrieb 5 60 Mi nuten vor der ON Zeitein stellung Die Vorzugseinstellung funktio niert nur f r COOL und HEAT Betrieb einschlie lich AUTO und n...

Page 35: ...e Luftstr mung und bewirken einen ung nstigen Be trieb Vermeiden Sie Stellen mit hoher Temperatur wie etwa elektrische Heizdecken oder einen Ofen Luftstr mungsrichtung sorgf ltig einstellen Luftstr mu...

Page 36: ...rme Reinigungsl sung verwenden 1 2 3 Vor der Wartung W hrend der Betriebssaison Luftfilter herausnehmen 1 Das Ansaugluftgitter nach vorne hoch ziehen 2 Die Kn pfe auf beiden Seiten erfassen und etwas...

Page 37: ...neutralisationsfilter aus der Klimaanlage 3 Nehmen Sie den bio Enzymfilter aus dem Filterhalter und pr fen Sie den Filter Verwenden Sie einen Staubsauger um Staub und Schmutz vom bio Enzymfilter zu en...

Page 38: ...n Ger ts und HEAT des anderen Ger ts nicht m glich Bei verschiedenen Bedienungsschritten erh lt die zuerst eingeschaltete Klimaanlage den Vorrang so da die danach eingeschaltete Klimaan lage auf Gebl...

Page 39: ...trieb FAN aktiviert Falls ein Ger t im Modus COOL l uft und ein anderes im Modus HEAT oder einer anderen Betriebsart wird der L fterbetrieb FAN aktiviert Passen Sie die einzelnen Betriebsarten aneinan...

Page 40: ...wieder eingeschaltet worden ist Ein Schalter funktioniert nicht ein wandfrei Ungew hnliche Ger usche w hrend des Betriebs 3 Minuten sind vor ber aber warum Sicherung brennt wiederholt durch Die RUN un...

Page 41: ...W rmetauschers 1 gebrochen mangelhafter Steckerkontakt Sensor unterbrochen Defekt des Innenanlagenventilators Defekt des W rmetauschersensors 1 Blinkt 2 mal Blinkt 5 mal Blinkt 1 mal RUN Lampe Blinkt...

Page 42: ......

Reviews: