background image

TX3-CX-1NP Installation

3

LT-5997 Rev 3 January 2018

Subject to change without notice. See http://www.mircom.com for the latest information

• Standard Wiegand interface
• LED status indicator
• Warning or alarm buzzer
• 12 Volt operation
• Maximum distance 500 ft (152.4 m)
• Use 20 AWG for 500 ft (152.4 m)
• Use 22 AWG for 250 ft (76.2 m)
• For other card readers, consult your reader installation manual for recommended distances 

and gauges

F.

Wiring TX3-CX-1NP

• RS-485 wiring maximum length: 1219.2 m (4000 ft)
• PoE maximum length: 100 m (328 ft)
• Wiegand connection maximum length: 152.4 m (500 ft)

Figure 4

Wiring TX3-CX-1NP

RS-485

Set the 120

 switch ON if unit is used as first or last controller on RS-485 network, and an 

external resistor is not used. Otherwise set OFF.

Shielded or unshielded Cat 5 cable

WIEGAND CONNECTIONS

22-16 AWG

DATA 0

GND

DATA 1

BEEP

LED (G)

PWR

INPUT 4

General purpose

22 AWG

INPUT 3

General purpose

22 AWG

INPUT 2

Request to Exit (built-in reader)

22 AWG

INPUT 1

Door contact (built-in reader)

22 AWG

LED (R)

RJ45 connector for Internet 
communication. Power can be provided 
through Power over Ethernet if not 
provided by the DC power terminals.

Micro USB port:

 

Connect to computer for network 
firmware upgrade and 
configuration
(maximum length of USB cable: 

 

8 feet/2.4 m)

12 VDC / 15 W 

Input power
18 AWG

24-48 VDC / 15 W

Input power (20-18 AWG)

OUTPUT 1

Door Lock
18 AWG

OUTPUT 2

General purpose
18 AWG

OUTPUT 3

 

12 VDC/700 mA max. 
solid state output for a 

DC lock
22-18 AWG

DIP switches for setting RS-485 address

+

-

+

-

+

-

NC
C
NO

NC
C
NO

RS-485

+

-

S

Recommended distance and gauge for TX3 card readers: 
Use 20 AWG for 152.4 m (500 ft)
Use 22 AWG for 76.2 m (250 ft)
For other card readers, consult your reader installation 
manual for recommended distances and gauges.

Outputs 1 and 2 are relay contact
programmable outputs with the
following characteristics:
normally open (NO)
normally closed (NC) available
30 VDC/2 A or
125 VAC/0.5 A

Set ON if unit is used as first or last controller on 
RS-485 network, and an external resistor is not 
used. Otherwise set OFF.

Summary of Contents for TX3-CX-1NP

Page 1: ...anuals B Mount TX3 CX 1NP 1 Mount TX3 CX 1NP on the two posts as shown in Figure 1 2 Secure it with the provided nuts Figure 1 Mount TX3 CX 1NP C Mount the TX3 P300 HA Card Reader Secure the card reader to the plastic bracket on the inside of the door with the 2 6 32 x 1 2 screws that are included with the TX3 unit Note Do not use the cover that is included with the reader Note Install the reader ...

Page 2: ... an IP address from the DCHP server Set DIP switch 8 on to set a fixed IP address using the TX3 Configurator software For more information and the complete list of RS 485 addresses see LT 980 the TX3 Card Access System Manual on the Mircom website www mircom com or the USB flash E Connect the Card Reader Card reader requirements Card readers must meet the following minimum requirements in order to...

Page 3: ...2 Request to Exit built in reader 22 AWG INPUT 1 Door contact built in reader 22 AWG LED R RJ45 connector for Internet communication Power can be provided through Power over Ethernet if not provided by the DC power terminals Micro USB port Connect to computer for network firmware upgrade and configuration maximum length of USB cable 8 feet 2 4 m 12 VDC 15 W Input power 18 AWG 24 48 VDC 15 W Input ...

Page 4: ...SB flash Outputs For details on programming the outputs see LT 995 on the Mircom website www mircom com or the USB flash G Connect the Power The Single Door Controller can be powered in three ways Power over Ethernet PoE 12 VDC 15 W 24 57 VDC 15 W H Card Reader Beeper The beeper indicates specific events at different beep rates as follows Card Presented One short beep Access Granted Two short beep...

Reviews: