Appendix D: Power Supply and Battery Calculations
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model Number
Description
Qty
STANDBY
TOTAL
STANDBY
ALARM TOTAL
ALARM
FX-350-60-DR
Main Panel c/w Dialer
X
0.220
=
0.380
=
FX-351-LW
FX-353-LW
Main Panel c/w 1 RAX-
332 LED Displays
X
0.210
=
0.390
(Note 1)
=
FX-351-LDW/R
FX-353-LDR
Main Panel, c/w 1 RAX-
332 LED Displays and
Dialer
X
0.230
=
0.400
(Note 1)
=
ALC-252
252 Point Dual Loop
Addressable Adder
x
0.120
=
0.230
=
RAX-332 32
LED
Display
X
0.005
=
0.010
=
PR-300
Polarity Reversal and
City Tie Module
X
0.050
=
0.300
=
RAM-300-
LCDW/R
Remote LCD
Annunciator
X
0.016
=
0.040
=
RAM-208
Remote Annunciator, 8
Zone LED
X
0.0350
=
0.090
=
RAM-216
Remote Annunciator, 16
Zone LED
X
0.0350
=
0.140
=
RTI-1
Remote Trouble
Indicator
X
0.035
=
0.035
=
MIX-3000
Ionization Detector
X
0.00028
=
0.00028
=
MIX-3100
Photoelectric Detector
X
0.0004
=
0.0034
=
MIX-3200
Multi-sensor Detector
X
0.0005
=
0.0035
=
MIX-3300
Heat Detector
X
0.0005
=
0.0034
=
MIX-100P
Priority Monitor Module
X
0.0006
=
0.0046
=
MIX-101P
Mini Priority Monitor
Module
X
0.0006
=
0.0046
=
MIX-100R
Relay Output Module
X
0.00085
=
0.0035
=
MIX-100S
Supervised Control
Module
X
0.00100
=
0.00100
=
MIX-100X (Kit)
100XH (Isolator)
100XB (Base)
Isolator c/w Mounting
Base
X
0.000035
=
0.000035
=
MIX-2001R
Relay Base
X
0.0
=
0.046
=
Device & Remote LEDs (Maximum 30)
X
0.0040
=
Signal Load (bells, horns, strobes, and etc.)
X
=
Auxiliary Power Supply for Annunciators, etc. (See Note 2)
=
=
Total currents (Add above currents) STANDBY(