Indicators, Controls and Operations
36
Buzzer Silence LED
The Buzzer Silence LED flashes amber at the Trouble Flash rate when the Buzzer Silence button is pressed. Any
new alarm, supervisory or trouble events will resound the buzzer and will cause the Buzzer Silence LEd to turn off.
Acknowledge LED
If the panel is configured as a two stage system, the Acknowledge LED flashes amber at the Fast Flash rate while
the General Alarm timer is timing. It turns ON steady amber after the Auto General Alarm Timer is cancelled by the
activation of the Acknowledge or Signal Silence buttons. If the Auto General Alarm Timer times-out and puts the
panel into General Alarm, the Acknowledge LED turns OFF. If the panel is configured as Positive Alarm Sequence
(PAS), the Acknowledge LED flashes amber at the Fast Flash rate while a timer counts down 15 seconds to
common alarm.
General Alarm LED
In two stage operation only, the red General Alarm LED illuminates steadily after the General Alarm button is
pressed, or after the Auto General Alarm Timer times out. Once the General Alarm LED turns ON it will stay active
until the panel is reset.
Lamp Test LED
The amber Lamp Test LED will illuminate steadily after the Lamp Test button is pressed and while system is in Lamp
Test mode.
Battery/Charger Trouble LED
In a ULI application the amber Battery/Charger Trouble LED flashes at the Trouble Flash rate when any Battery/
Charger Trouble occurs.
In a ULC application the amber Battery/Charger Trouble LED illuminates steady when any Battery/Charger Trouble
occurs.
LEDs 1 to 32 for FX-351 and FX-353 Series Only
Points labelled 1 to 32 are available for alarm, supervisory, and monitor annunciation (bi-coloured red/amber LEDs)
and trouble annunciation (amber LEDs).
RAX-332 LEDs 33 to 64 for FX-351 and FX-353 Series Only
Points labelled 33 to 64 are available for alarm, supervisory, and monitor annunciation (bi-coloured red/amber
LEDs) and trouble annunciation (amber LEDs).
Common Controls
LCD Display
The display is a two line, 20 character back-lit alphanumeric LCD. It displays information regarding the panel, its
circuits, and devices. An on-screen cursor is controlled by the cursor buttons (located to the right of the display) for
menu selection and control. Report information provided by the LCD display includes Alarm, Event Log, Current
Levels, Verification, and Maintenance reports.
Cursor Buttons
Located at key number 2, 8, 6 and 4. The cursor buttons Up (next), Down
(previous), Right, and Left allow you to select items on the LCD display.
The Up and Down buttons scroll through lists in a continuous loop.
Enter Button
Use this button to select a displayed item on the LCD display.
Cancel Button
Use this button to cancel an operation or exit a menu.
1
2
ABC
3
DEF
5
JKL
6
MNO
7
8
TUV
9
WXY
*
0
QZ
#
4
GHI
PRS
X
M
?
X
Summary of Contents for FX-350 Series
Page 2: ......
Page 6: ...List of Figures Tables vi ...
Page 57: ......
Page 58: ......
Page 59: ......