DIP Switch Settings

4.1  The RAX-1048 Adder 

Annunciator Chassis

P1:

 Connects to the main annunciator

chassis, or to the previous RAX-1048TZ
or IPS-2424.

P2:

 Connects to the next RAX-1048TZ or

IPS-2424.

4.2  The IPS-2424 

Programmable Input 
Switches Module

P1: 

Connects to the main annunciator

chassis, or to the previous RAX-1048TZ
or IPS-2424.

P2: 

Connects to the next RAX-1048TZ or

IPS-2424.

Table 3  Annunciator “Address” Settings

Address

SW1-1

SW1-2

SW1-3

SW1-4

SW1-5

Address

SW1-1

SW1-2

SW1-3

SW1-4

SW1-5

33

OFF

ON

ON

ON

ON

49

OFF

ON

ON

ON

OFF

34

ON

OFF

ON

ON

ON

50

ON

OFF

ON

ON

OFF

35

OFF

OFF

ON

ON

ON

51

OFF

OFF

ON

ON

OFF

36

ON

ON

OFF

ON

ON

52

ON

ON

OFF

ON

OFF

37

OFF

ON

OFF

ON

ON

53

OFF

ON

OFF

ON

OFF

38

ON

OFF

OFF

ON

ON

54

ON

OFF

OFF

ON

OFF

39

OFF

OFF

OFF

ON

ON

55

OFF

OFF

OFF

ON

OFF

40

ON

ON

ON

OFF

ON

56

ON

ON

ON

OFF

OFF

41

OFF

ON

ON

OFF

ON

57

OFF

ON

ON

OFF

OFF

42

ON

OFF

ON

OFF

ON

58

ON

OFF

ON

OFF

OFF

43

OFF

OFF

ON

OFF

ON

59

OFF

OFF

ON

OFF

OFF

44

ON

ON

OFF

OFF

ON

60

ON

ON

OFF

OFF

OFF

45

OFF

ON

OFF

OFF

ON

61

OFF

ON

OFF

OFF

OFF

46

ON

OFF

OFF

OFF

ON

62

ON

OFF

OFF

OFF

OFF

47

OFF

OFF

OFF

OFF

ON

63

OFF

OFF

OFF

OFF

OFF

48

ON

ON

ON

ON

OFF

P2

        RAX-1048(TZ) Adder Annunciator or
IPS-2424 Programmable Input Switches Module

P1

   POWER
TERMINALS

SW1

P1

RAX-LCD SHARED DISPLAY   BOARD

    RS-485
TERMINALS

ALARM

QUEUE

SUPV.

QUEUE

TROUBLE

QUEUE

MONITOR

QUEUE

Mircom FX-2000

Fire Alarm Control Panel

Normal Condition

February 14, 2001

SIGNAL

SILENCE

GENERAL

ALARM

ACKNOW-

LEDGE

FIRE

DRILL

SYSTEM

RESET

LAMP

TEST

ENTER

MENU

CANCEL

INFO

GROUND

FAULT

PRE-

ALARM

A.C.

ON

P2

Figure 4    Annunciator Connections

firealarmresources.com

Summary of Contents for FX-2000 series

Page 1: ...0 4113 www mircom com RAX LCD Remote FX 2000 Annunciator Panel LT 856 Rev 7 1 November 2011 Installation and Wiring Manual Advanced Life Safety Solutions Mircom FX 2000 Fire Control System System Norm...

Page 2: ...firealarmresources com...

Page 3: ...dels 15 5 2 1 RAX LCD Remote FX 2000 Shared Display LCD Annunciator 15 5 2 2 RAX 1048TZ Adder Annunciator Chassis 48 Display Points 15 5 3 Current Drain for Battery Calculations 16 5 4 Environmental S...

Page 4: ...e 19 6 3 12 Inadequate Testing 19 6 3 13 Security and Insurance 19 6 4 Limited Warranty 19 6 4 1 International Warranty 19 6 4 2 Conditions to Void Warranty 20 6 5 Warranty Procedure 20 6 6 Disclaimer...

Page 5: ...echanical Assembly Diagram 9 Figure 2 Wiring Diagram 10 Figure 3 Annunciator Panel Connections 10 Table 2 Maximum Wiring Run to Last Annunciator 11 Figure 4 Annunciator Connections 13 Table 3 Annuncia...

Page 6: ...6 List of Figures and Tables firealarmresources com...

Page 7: ...it alphanumeric LCD display that uses a simple menu system complete with a directional keypad and switches for Enter Menu Cancel and Info The display expands with up to a total of four RAX 1048TZ Adde...

Page 8: ...al 905 660 4655 Email mail mircom com 1 1 2 Customer Service Toll Free 1 888 MIRCOM5 North America Only Local 905 695 3535 Toll Free Fax 1 888 660 4113 North America Only Local Fax 905 660 4113 Email...

Page 9: ...BB 1012 45 0 20 9 52 0 Note The RAX 1048 normally displays Initiating circuit status no individual circuit troubles however model RAX 1048TZ will allow individual circuit trouble indication as well In...

Page 10: ...r the number of annunciators and the total wiring run length Use the Current Drain for Battery Calculations on page 16 to calculate the maximum current for all annunciators summed together 24 VDC INPU...

Page 11: ...to which it is connected Table 2 Maximum Wiring Run to Last Annunciator Max for all Annunciators Max Loop Resistance 18AWG 16AWG 14AWG 12AWG Amperes ft m ft m ft m ft m Ohms 0 12 1180 360 1850 567 30...

Page 12: ...3 SW1 5 Address A4 DIP switches are for assigning an address to the RAX LCD Binary addresses 33 to 63 are available with the least significant bit being switch SW 1 and the most significant bit being...

Page 13: ...N OFF OFF ON ON 54 ON OFF OFF ON OFF 39 OFF OFF OFF ON ON 55 OFF OFF OFF ON OFF 40 ON ON ON OFF ON 56 ON ON ON OFF OFF 41 OFF ON ON OFF ON 57 OFF ON ON OFF OFF 42 ON OFF ON OFF ON 58 ON OFF ON OFF OFF...

Page 14: ...1 Connects to the first RAX 1048TZ or IPS 2424 P2 BDM port Terminals See Wiring Instructions on page 10 for details SW1 See above for details Note The last annunciator must have 120 ohm E O L resistor...

Page 15: ...rconnect via one ribbon cable from RAX LCD or to previous RAX 1048TZ or IPS 2424 to the next RAX 1048TZ or IPS 2424 Annunciation of up to 48 additional points Standby 15 mA Max All LEDs On 100 mA Max...

Page 16: ...mum 150 mA ___________ X 15 mA _________ X 144mA __________ number of RAX 1048TZ number of IPS 2424 Use the normal standby current for battery size calculations see the fire alarm control panel manual...

Page 17: ...isdiction Such inspections ensure installation has been carried out properly 6 3 2 Power Failure Control units smoke detectors and many other connected devices require an adequate power supply for pro...

Page 18: ...ect to those products Mircom does not warranty that the operation of the software will be uninterrupted or error free or that the software will meet any other standard of performance or that the funct...

Page 19: ...ty and Insurance Regardless of its capabilities an alarm system is not a substitute for property or life insurance An alarm system also is not a substitute for property owners renters or other occupan...

Page 20: ...ization has not been obtained NOTE Unless specific pre authorization in writing is obtained from Mircom management no credits will be issued for custom fabricated products or parts or for complete fir...

Page 21: ...ecommends that the entire system be completely tested on a regular basis However despite frequent testing and due to but not limited to criminal tampering or electrical disruption it is possible for t...

Page 22: ...firealarmresources com...

Page 23: ...firealarmresources com...

Page 24: ...ircom 2011 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 905 660 4655 Fax 905 660 4113 TECHNICAL...

Reviews: