4.0
DIP Switch Settings
Each RAX-LCD Shared Display Annunciator needs to be assigned a unique address via the
switch SW1.
The RAX-LCD DIP switches are set as:
The OFF setting is active. The addresses available for the RAX-LCD are 33 to 63. Set the
address as follows in the table below:
SW1-1
= Address
A0
SW1-2
= Address
A1
SW1-3
= Address
A2
SW1-4
= Address
A3
SW1-5
=
Address A4
DIP switches are for assigning an address to the RAX-LCD.
Binary addresses 33 to 63 are available with the least
significant bit being switch SW-1 and the most significant bit
being SW-6. The OFF setting is active binary. DIP switches
SW1-7 and SW1-8 are not used. For example, address 33 is
set by setting SW1-6 and SW1-1 OFF and all the other DIP
switches are ON.
SW1-6
=
Address A5(OFF)
SW1-7
=
not used
SW1-8
=
Put in “OFF” position
for firmware restore
during power up. At
all other times put in
“ON” state.