2
•
MGC Protocol Quad Loop Adder module ALCN-960MISO for expanding addressable
loops (SLC) by 2; with daughter board ALCN-960D expanding addressable loops by a
total of 4. Each SLC Loop is set to function with MGC MIX-4000 Series addressable
modules (240 sensors and modules) and can be wired as Class A (Class X) or Class B.
•
AP Protocol Quad Loop Adder module ALCN-4792MISO for expanding addressable
loops (SLC) by 2; with daughter board ALCN-792D expanding addressable loops by a
total of 4.
•
12 Ampere Power Supply.
•
Four Class A or B NACs rated at 1.7 Amperes each, which can be configured as Audible
or Visual (silenceable or non-silenceable circuits). Audibles may be steady, Temporal
Code, California Code, or March Time.
•
Indicating circuits (NACs) may be configured to provide additional auxiliary power or
resettable auxiliary power. NAC expansion using the INX-10A, INX-10ADS or INX-10AC.
•
Fault isolators are present on all in-panel addressable loops.
•
Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, Assisted
Walk Test.
•
Outputs for 4 Wire resettable Smoke Power Supply, Auxiliary Power Supply, and an
interface to the Mircom RTI-1 Remote Trouble Indicator.
•
RS-485 Interface for Remote Annunciators. Remote Annunciators do not occupy a node
on the network. Up to seven annunciators can be connected per node.
•
Three Level Password Protection with field settable definition which enables the installer
to determine what functions are accessible for each level of password
•
Four queues for acknowledge with Alarm Queue, Supervisory Queue, Trouble Queue,
and BLDG (Monitor) Queue LED indicators and pushbuttons.
•
Auxiliary Form-C Relay Contacts for Common Alarm, Common Supervisory, and
Common Trouble.
•
RS-232 Port for remote system printer or “CRT terminal”.
•
Two Event History Logs; one for Alarm related events and one for all events.
•
Common Controls and Indicators for System Reset, Lamp Test (Visual Indicator Test),
Fire Drill, Signal Silence, General Alarm, General Alarm Cancel (Automatic Alm Sig
Stop), AC On, CPU Fault, and Ground Fault.
•
Two Spare configurable switches and LED Indicators.
•
16 Zone configurable LED (bi-coloured) Annunciator with slide-in labels for Zone
Description with the DSPL-420-16TZDS Display.
•
Provides drift compensation for ionization and photoelectric smoke detectors
•
Provides Signal Coding of signal circuits for easy alarm identification (code consists of 1
to 4 digits, each digit consisting of 1-15 pulses on the signal)
•
Selection for Canadian (ULC) or USA (ULI) requirements for Smoke Sensor sensitivity.
•
Extensive transient protection.
•
Surface Mountable Enclosures with removable doors for easy installation and service.
Flush trims available.
•
Removable Terminal Blocks for easy wiring and service.
•
OPEN Graphic Navigator Software Package
allows 3D graphic display of premises
and devices. Use the Ethernet port on the main board to connect to OpenGN graphics
software.