114
Figure 72
QMP-5101NV and QMP-5101N Network Master Paging Control Module
Connections and Terminal Blocks
The interface wiring between the QMP-5101NV/N and ANC-4000 is as follows:
The maximum wiring run from the QMP-5101NV/N and the ANC-4000 is 20 feet or 6 metres.
MIC+, MIC-, SHLD:
18-22 AWG Twisted Shielded Pair
PTT+, PTT-:
18-22 AWG Twisted Pair
CABLE CONNECTS TO PREVIOUS DISPLAY MODULE
FROM PREVIOUS
MICROPHONE
TO NEXT
MICROPHONE
(IF THIS IS THE LAST
MICROPHONE,
PLACE
EOL 3K9 ohm
RESISTOR HERE
B and -
OF PTT TERMNALS).
P1
P2
SHIELD
SHIELD
MIC IN
MIC OUT
SHIELD
SHIELD
PT
T OUT
PT
T IN
TO QAZT-5348DS or QAZT-5302DS SELEC-
TOR PANEL OR NEXT DISPLAY MODULE