139
ANC-4000 Board Address Setting (DIP SWITCH SW1)
ALCN-960MISO/ALCN-4792MISO Loop Adder Module Address Setting (DIP SWITCH SW1)
RAXN-4000LCD/RAXN-4000LCDG Remote Annunciator Address Setting (DIP SWITCH SW1)
40.0
Appendix D: Alarm Verification Timing
A Manual Station, or other contact-closure device, would remain shorted and be detected during the very short
Zone Power burst within the first three seconds. A Smoke Detector will have been reset, and will require some
minimum time to power-up, thus the Verification cycle will be entered.
ANC-4000
ADDR
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
2
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
3
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
4
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
5
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
6
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
7
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ALCN-9
60MISO
ALCN-4792MISO
ADDR
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
1
ON
OFF
OFF
OFF
OFF
OFF
OFF
Put in "
O
N"
position for
fir
m
w
are rest
ore t
o
def
aul
ts
du
ring po
wer up.
A
t all
o
the
r
times put
in "O
F
F
"
st
at
e.
2
OFF
ON
OFF
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
OFF
OFF
5
ON
OFF
ON
OFF
OFF
OFF
OFF
6
OFF
ON
ON
OFF
OFF
OFF
OFF
7
ON
ON
ON
OFF
OFF
OFF
OFF
RAXN-4000LCD(G)
ADDR
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
33
ON
OFF
OFF
OFF
OFF
ON
Leave in "OFF"
position as
Factory Set.
34
OFF
ON
OFF
OFF
OFF
ON
35
ON
ON
OFF
OFF
OFF
ON
36
OFF
OFF
ON
OFF
OFF
ON
37
ON
OFF
ON
OFF
OFF
ON
38
OFF
ON
ON
OFF
OFF
ON
39
ON
ON
ON
OFF
OFF
ON
SMOKE DETECTOR
IN ALARM
3s
1s
10s
(30s)
(65s)
ULI/ULC Retard / Reset / Restart
60 seconds Maximum
Reset
Restart
ULI/ULC Confirmation Period
60 seconds Minimum
These intervals are determined
by the maximum Detector Reset
time, which is 1s for our uses.
This interval is determined by the maximum
Detector Start-up time. ULC states a maximum hold
time of 30 seconds.