-3-
5.5 BATTERY FAULT LED
Battery removal, low voltage and open battery leads will turn on the yellow
battery fault
LED and
the
common trouble
LED.
5.6 GROUND FAULT LED
Any ground fault of 10K ohms or less will turn on the yellow
ground fault
LED steadily, flashing
the
common trouble
LED and sounding the
common trouble
buzzer intermittently.
5.7 SIGNAL TROUBLE LED
The yellow
signal trouble
LED will illuminate steadily for any open or short.
(The LED is located behind the display plate.)
6. SEQUENCE OF OPERATION
Refer to Figure 2 for the location of indicators and controls.
6.1 NORMAL
All indicators are normally OFF except for the green
A.C. On
LED.
6.2 ALARM
A red zone
alarm
LED will illuminate steadily for incoming alarm.
6.3 SIGNAL SILENCE
If the
60 second signal silence
inhibit is selected, the signal cannot be silenced for 60 seconds
after an alarm initiation. Once the 60 seconds have expired, pushing the
signal silence
switch to
the right will silence all the bells and horns. Once the signal has been silenced, the
signal
silenced
LED will illuminate. If the switch is in the
off
normal position to the right while there
is no alarm condition, the panel will indicate trouble.
6.4 RESET
Operating the
reset
switch will restore all latched functions in the panel. The smoke detectors will
reset if all products of combustion are cleared from their chambers.
Summary of Contents for FA-101U
Page 7: ... 5 FIGURE 1 BACKBOX FLUSH TRIM MOUNTING DETAILS ...
Page 8: ... 6 FIGURE 2 CIRCUIT BOARD LAYOUT ...
Page 9: ... 7 FIGURE 3 DETECTION AND SIGNAL WIRING INSTRUCTION ...
Page 10: ... 8 FIGURE 4 WIRING TABLE FOR DETECTION ZONE ...
Page 11: ... 9 FIGURE 5 WIRING TABLE FOR BELLS AND HORNS ...
Page 12: ... 10 FIGURE 6 ALARM AND TROUBLE RELAY CONTACTS AND REMOTE ANNUNCIATION WIRING INSTRUCTIONS ...
Page 17: ......
Page 18: ...Notes ...
Page 19: ......