background image

SNMP-SSL 

25 

Client Table 

 
Select Client Table from the UPS Monitoring on the main menu to get a list of the 
connected clients, which are running the shutdown software. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 3-8 SNMP-SSL Client Table 

 

Summary of Contents for SNMP-SSL

Page 1: ...SNMP SSL UPS SNMP Card Web Based monitoring SNMP Card User s Manual...

Page 2: ...S Battery Test 27 UPS Battery Test Schedule 28 UPS Shutdown 29 Weekly Schedule 30 Special Day Schedule 30 EMD Configuration 31 Chapter 5 SNMP SSL Management 32 Date and Time 32 SNMP SSL Configuration...

Page 3: ...ndows 95 98 Me Windows NT 2000 XP 2003 are registered trademarks of Microsoft Corporation All other trademarks belong to their respective proprietors Electronic Emission Notice Federal Communications...

Page 4: ...via Java Applets Provides visual indication on screen through dynamic graphics Keep event logs metering data in flash memory Provides a history file of the UPS power events power quality status and b...

Page 5: ...P SSL card is an interface between UPS and the network It can obtain the status from a UPS and issue commands to it SNMP SSL card supports two kinds of protocol SNMP and HTTP for user access Through t...

Page 6: ...tion Note The SNMP SSL cards are designed to be Hot Swappable but there is a remote chance that when Hot Swapping the SNMP SSL card that the UPS will shutdown MINUTEMAN recommends following steps 1 th...

Page 7: ...the workstation 2 Set both the DIP switches of the SNMP SSL card to the OFF position operating mode for configuration Figure 2 2 Serial cable connection of SNMP SSL 3 From a workstation running Micro...

Page 8: ...d choose an icon for the connection and then click OK Figure 2 4 New HyperTerminal connection 5 Select direct COM port connection Select the appropriate COM port and then click OK Figure 2 5 Select Di...

Page 9: ...rol then click Apply and then OK Figure 2 6 Setup of the COM port parameters 7 Power on the UPS and wait for SNMP SSL card to boot up Hit the Enter key once to display the menu below Enter the passwor...

Page 10: ...l be displayed Select 1 to enter the SNMP SSL Configuration Menu Figure 2 8 SNMP SSL Configuration Utility Main Menu 9 The SNMP SSL Configuration Menu will be displayed Select 1 to enter the System Gr...

Page 11: ...e able to connect to the SNMP SSL card with a Web Browser All other setting may be configured using a Web Browser except for changing the Login Password Figure 2 10 System Group Configuration Menu Aft...

Page 12: ...Figure 2 12 SNMP SSL Control Group Configuration Menu After completing these settings select 0 to return to the Configuration Menu 13 In the Configuration Menu select 3 to configure the SNMP SSL para...

Page 13: ...settings Figure 2 14 Email Group Configuration Menu After completing these settings select 0 to return to the Configuration Menu 15 In the Configuration Menu select 5 to configure the Web Authenticati...

Page 14: ...nu After completing these settings select 0 to return to the Configuration Menu 17 In the Configuration Menu select 6 to configure the Ping Group settings Figure 2 17 Ping Group Configuration Menu Aft...

Page 15: ...d only when using the Community Read Write password in Control Group The community strings entered in the Community String fields are visible only through the RS 232 connection The Telnet connection d...

Page 16: ...SSL Configuration Utility Main Menu select 5 to configure the Trap Receiver settings If you want to use a PC to perform the SNMP manager trap function in order to manage UPS through SNMP SSL card the...

Page 17: ...e that you have a TCP IP network already installed 2 Connect the network cable to the Network port on the SNMP SSL card 3 Run command shell i e Windows MS DOS prompt 4 SNMP SSL card will initially try...

Page 18: ...b Browser 1 From a workstation running Microsoft Windows 9x Me NT4 0 2000 XP 2003 or later set up the TCP IP protocol if necessary 2 Connect the network cable to the Network port on the SNMP SSL card...

Page 19: ...e Become Administrator button at the bottom of the page Enter SNMP SSL as the login name and admin as the password Case sensitive 8 Enter the IP Address 9 Enter the Gateway Address 10 Enter the Subnet...

Page 20: ...and time information 14 When finished click Set Value to save the settings Figure 2 24 SNMP SSL Date and Time page 15 Open the SNMP SSL Control page 16 Make the appropriate changes 17 When finished cl...

Page 21: ...l be displayed UPS Monitoring This main menu contains all the measurements and data read from the UPS All the sub menus are read only for all users write mode access is not allowed Comprehensive View...

Page 22: ...ch page for a detail description of each item Figure 3 2 SNMP SSL Help Menu UPS Identification Select the UPS Identification from the UPS Monitoring menu of the home page to get the UPS and SNMP SSL c...

Page 23: ...the UPS Monitoring on the main menu to get the UPS s battery parameters Figure 3 4 SNMP SSL Battery Parameters Input Parameters Select Input Parameters from the UPS Monitoring on the main menu to get...

Page 24: ...from the UPS Monitoring on the main menu to get the UPS s output parameters Figure 3 6 SNMP SSL Output Parameters Alarm Table Select Alarm Table from the UPS Monitoring on the main menu to get the sta...

Page 25: ...SNMP SSL 25 Client Table Select Client Table from the UPS Monitoring on the main menu to get a list of the connected clients which are running the shutdown software Figure 3 8 SNMP SSL Client Table...

Page 26: ...will not be able to perform any configuration on SNMP SSL UPS See the Access Control Table Setting and the SNMP HTTP Access Control for details This menu contains the control parameters of the UPS Al...

Page 27: ...lue to save the settings Figure 4 2 SNMP SSL UPS Control UPS Battery Test This menu allows you to perform two battery tests and provides information about the last battery test performed 1 Quick Batte...

Page 28: ...battery testing for a specific day and time 1 Quick Battery Test Test the battery for 10 seconds 2 Test Until Battery Low Test the UPS until a Low Battery Warning occurs then resets to the AC mode 3...

Page 29: ...ed SNMP SSL card will take the selected action as define in the Shutdown Actions column Available actions are a Disabled Action is disabled b Warning Warning message will be broadcast to the connected...

Page 30: ...perform this action every week at the designated time When finished click Set Value to save the settings Figure 4 6 SNMP SSL Weekly Schedule Special Day Schedule This menu allows you to modify the par...

Page 31: ...n Offset setting can be configured to adjust the final value of the sensor 4 Alarm Type If an alarm sensor water leak security etc is connected to the SNMP SSL card the user can configure the alarm as...

Page 32: ...his menu allows the administrator to set the local network configuration parameters for the SNMP SSL card The basic variables for SNMP management can also be set 1 SNMP SSL IP Address The IP address o...

Page 33: ...ltage Load Capacity Battery temperature and Input frequency These values are saved in the History Log The maximum value for this setting is 28800 seconds i e 8 hours 11 Extended History Log Interval T...

Page 34: ...erver application Telnet control process The standard port is 23 5 HTTP Support Enabling or disabling the HTTP connection with the SNMP SSL card The user may configure HTTP protocol to use a port numb...

Page 35: ...ator to flash upgrade the SNMP SSL card s firmware 1 Browse Searches for the location where the firmware file Bin is stored 2 Upgrade Agent Firmware Starts the upgrade process 3 Upload Status Shows th...

Page 36: ...t shows the RADIUS UDP port 2 Primary RADIUS Server Set the Primary RADIUS Server s IP address 3 Secondary RADIUS Server Set the Secondary RADIUS Server s IP address 4 Share Secret of Primary Server S...

Page 37: ...the user to change the Trap Level for each Trap 1 Index The index number of the entry in the table 2 Trap Name The short description of each Trap 3 Trap Level There are three levels that can be select...

Page 38: ...by the Administrator 4 Access Type Access right associated with the IP Address Available options are a NotAccess b Read c Read Write If the IP Address is set to NotAccess or Read not even the administ...

Page 39: ...user name who will have access to the SNMP SSL card via SNMPv3 3 Auth Password This field allows the administrator to set the authentication password of the associated user 4 Priv Password This field...

Page 40: ...ceiver 19 characters are the maximum length of the string 4 Trap Type Types of traps to be received a None No traps are to be received b RFC 1628 Trap Traps are received base on RFC 1628 c SNMP SSL Tr...

Page 41: ...of times the packets will be sent 2 Interval Timer Sec The time before the next packet is sent 3 Set Value Saves the settings 4 Index The index number of the entry in the table 5 MAC Address The MAC a...

Page 42: ...no entry The User Account is only required if Mail Server requires authentication to send emails 3 User Password The User Password is for the User Account 4 SMTP Authentication This is only required...

Page 43: ...y Status Report At hh mm must be set up to perform this function d Events Status Allows the designated recipient to receive event notifications and the Daily Status Reports When a specific event occur...

Page 44: ...al support homepage 1 Screen Text This is the description of the hyperlink name which will be displayed on the menu tree 2 Link Address This field defines the web page location to be connected The add...

Page 45: ...ximum number of entries rows has been reached The Administrator has the access right to delete the log file 1 Log Date Date on which the entry was made 2 Log Time The time in a 24 hour format when the...

Page 46: ...he ending date of the consolidation interval 4 End Time The ending time of the consolidation interval 5 Input Voltage The minimum maximum and average values of the input voltage in Volts 6 Output Volt...

Page 47: ...maximum number of entries rows has been reached The Administrator has the access right to delete the entries of the table Note To Save or Clear the log files go to the Clear Save Log Data menu 1 Date...

Page 48: ...en when the maximum number of entries rows has been reached The Administrator has the access right to delete the entries of the table Note To Save or Clear the log files go to the Clear Save Log Data...

Page 49: ...data as you click the hyper link below Administrator can choose to Clear the Log file after saving the Log file Select Yes or No and then click the Apply button Default value is set to No 3 Save Log...

Page 50: ...ded History Log Java Monitor By clicking the Java button at the top right hand side of the SNMP SSL card s Home Page a Java Applet will be opened in a separate window This applet displays the UPS s ke...

Page 51: ...ssage broadcast Enabled or disable the event message dialog box Exit Exit from the Java applet Status Bar Figure 7 3 Status Bar in the UPS Monitoring The status bar displays the current status of the...

Page 52: ...y combination of the parameters to be displayed on the graph by checking the check box beside each parameter and then click the Refresh button Display Point Displays the log interval on the graph Refr...

Page 53: ...tion of the parameters to be displayed on the graph by checking the check box beside each parameter and then click the Refresh button Display Point Displays the log interval on the graph Refresh Updat...

Page 54: ...PDA WAP Please input SNMP SSL card s address WAP or SNMP SSL card s address W Example HTTP 192 168 11 100 WAP or HTTP 192 168 11 100 W you can see the UPS s status page UPS Status UPS Status On Line...

Page 55: ...P or SNMP protocols Note If you do not enter the IP address of the workstation to the Access Control Table via Serial Port or Telnet or the SNMP HTTP Access Control via Web Browser in the SNMP SSL car...

Page 56: ...graceful shutdown of the server Installing the Shutdown Software in Windows 1 Insert the SNMP SSL CD ROM into the CD ROM drive 2 Run the SD_SNMP SSL Service_4 20 exe program on the CD ROM 3 A dialog b...

Page 57: ...om a Web Browser 1 Open a Web Browser and input the IP address of the SNMP SSL card 2 Select the Client Table from the UPS Monitoring folder A list of the connected devices will be shown on the screen...

Page 58: ...will be shutdown automatically if nothing is selected after the counter has counted down to zero Figure 9 3 Shutdown warning message There are five states for the shutdown software 1 UPS Connection OK...

Page 59: ...Local 6 Select a Device File and enter the name of the Mount Point Ex mnt Then select OK 7 Copy the shutdown programs into the directory and extract the programs to the directory of uGuard a mkdir uG...

Page 60: ...pecial shutdown script ShutdownScript usr foo ForceShutdownDelay The delay time for executing shutdown program Range from 0 to 65536 seconds ForceShutdownDelay 120 Check AC Fail event 1 TRUE 0 FALSE d...

Page 61: ...uGuard parameters use the following command cd uGuard uGuard h Figure 9 5 uGuard Parameters Description Deleting uGuard 1 Unload uGuard cd etc uGuard U 2 Remove uGuard files cd etc rm uGuard rm uGuard...

Page 62: ...ready mounted the CD ROM drive skip to step 7 4 Type mount dev cdrom 5 Change the directory to the Mount Point Ex mnt cdrom CLIENT Linux 6 Copy the shutdown programs into the directory and extract the...

Page 63: ...extract the programs to the directory of uGuard and then uncompress it 6 Type install sh to proceed with the installation procedure 7 The shell command will invoke the vi uGuard conf the user must mo...

Page 64: ...SNMP SSL 64 8 Type y yes to start the shutdown daemon uGuard Command Descriptions...

Page 65: ...SNMP SSL 65 1 Execute uGuard d command to suspend shutdown daemon 2 Execute uGuard r command to resume shutdown daemon 3 Execute uGuard p command to probe the shutdown daemon status...

Page 66: ...multiple SNMP SSL cards to upgrade 3 Select Modify and enter the User name and the Password 4 Select Open to find and load the new firmware file BIN 5 Select Upgrade to send the firmware file to the...

Page 67: ...te the following command line tftp tftp binary tftp connect host tftp put filename upgrade password username where binary Binary data download mode host SNMP SSL IP address Example 192 168 1 100 put P...

Page 68: ...SNMP SSL 68 Appendix B HTTP Security Control...

Page 69: ...0 C Operating Humidity 10 80 Power Input 8 15V DC Power Consumption 3 0 Watts Maximum Size L x W x H 5 1 x 2 4 x 0 7 inches 130 x 60 x 18 2 mm Weight 0 2 lbs 0 09 Kgs Regulatory compliance FCC class B...

Page 70: ...Phone Number If you are a consultant Consultant Name Phone Number Fax Number Computer System Operating System and version System Manufacturer System Model Number NMS name and revision number UPS Model...

Page 71: ...operating manual or other written instructions Any technical advice furnished before or after delivery in regard to use or application of Para Systems s equipment is furnished without charge and on t...

Reviews: