Function
Factory Default
User Choices
Description
UPS ID
Model number
Up to 64 characters to
define the UPS
Use this function to
uniquely identify the UPS
in your network
configuration
Battery install date
Date of manufacture
Date of battery
replacement -
day/month/year
XX/XX/XXXX
Enter the current date
when replacing batteries
Battery life in days
1826
Up to 5 characters
At first battery
replacement, reset to
reflect actual number of
days experience in your
environment or leave
factory default.
Enable/Disable auto
restart
Enabled
Enable or disable
When enabled, the UPS
will automatically restart
from a low battery
shutdown when normal
A/C returns
Set audible alarm state
Enabled
Enabled, at low battery,
disabled, Mute
Enabled - the UPS will
emit a short beep when in
the battery mode. At Low
Battery the UPS will emit
a steady tone only at low
battery warning through
shutdown.
Disabled - Use only when
software is controlling the
UPS or to silence the
alarm Mute - Attenuates
the alarm by 50%
Shutdown Type
UPS output
UPS output or UPS
UPS Output - When the
UPS is told to shut down,
it turns off the UPS output
only. UPS - Turns off the
UPS which requires the
UPS to be turned on
manually
Set low voltage Xfer point
92 VAC
(176 for 230VAC models)
92 or 88 VAC
(176 or 166 for 230VAC
models)
Changes the voltage
point at which the UPS
switches to battery power
Set high voltage Xfer
point
150 VAC
(282 for 230VAC models)
150 or 145 VAC
(282 or 272 for 230VAC
models)
Changes the voltage
point at which the UPS
switches to battery power
Set nominal input voltage
115 VAC
(230 for 230VAC models)
110,115,120 VAC
(220, 230, 240 for
230VAC models)
Changes the output
voltage
Baud Rate
9600
1200, 2400, 4800, 9600
Sets the communication
baud rate