Minuteman ED6200RM User Manual Download Page 3

 

2

1  Important Safety Instruction 

 

1.1. 

An Important Notice 

 
1.1.1  To ensure safety in all applications where a UPS system is hardwired to the 

electrical supply the UPS must be installed by a Qualified Electrical 
Contractor. 

 
1.1.2  The UPS has its own internal energy source (battery). If the UPS is 

switched on when there is no AC power is available, there could be voltage 
at the output terminals. 

 
1.1.3  Servicing of the UPS system must be performed by 

Qualified Service 

Personnel ONLY.

    MINUTEMAN accepts no liabilities and is not limited to: 

injury to the Service Personnel, or damages to; the UPS system, or the 
connected equipment caused by the incorrect installation or servicing of the 
UPS system. 

 
1.1.4  Make sure that the input voltage rating of the UPS matches the supply 

voltage. 

 
1.1.5  This UPS series is intended to be install in a temperature controlled 

environment that is free of conductive contaminants. Select a location that 
will provide good air circulation for the UPS at all times. Avoid locations near 
heating devices, water or excessive humidity, or where the UPS is exposed 
to direct sunlight. Route power cords so they cannot be walked on or 
damaged. 

 
1.1.6  To eliminate overheating of the UPS, keep all ventilation openings free from 

obstruction, and do not store anything on top of the UPS system. Keep the 
UPS system at least 12” (30 cm) away from the wall. 

 
1.1.7  The battery will discharge naturally if the UPS is unused for any length of 

time. The batteries should be recharged every 2-3 months if unused. 

 
1.1.8  This UPS supports electronic equipment in offices, telecommunications, 

process control, and medical applications. 

 
1.1.9  Risk of Electrical Shock. Make sure the UPS is completely turned off when 

moving the UPS from one location to another. 

 
1.1.10  The UPS has a Maintenance Bypass Switch. Follow the procedures to 

perform the maintenance bypass operation. 

 

 

3

1.1.11 

SAVE THESE INSTRUCTIONS

 - This manual contains important 

instructions that should be followed during the Installation and the 
Maintenance of the UPS and batteries. 

 

1.1.12 

CAUTION

 - A disconnect switch must be provided by the user for the AC 

output circuit when the UPS’s output is hardwired. To reduce the risk of fire, 
connect only to a circuit provided with branch circuit over-current protection 
for 40 amperes in accordance with the National Electric Code, ANSI/NFPA 
70. 

 

1.1.13 

CAUTION

 - To reduce the risk of fire, connect the input to a circuit provided 

with branch circuit over-current protection for 40 amperes in accordance 
with the National Electric Code, ANSI/NFPA 70. Use No. 8 AWG, 60

°

copper wire and apply 22.1lb-in Torque force when connecting to terminal 
block. 

 

1.1.14 

CAUTION

 - To reduce the risk of electrical shock with the installation of this 

UPS system and the connected equipment, the installer must ensure that 
the combined sum of the AC leakage current does not exceed 3.5mA. 

 

1.1.15 

WARNING

 - This Uninterruptible Power Supply (UPS) contains potentially 

hazardous voltages. Do not attempt to disassemble the UPS system 
beyond the battery replacement procedure. This UPS system contains no 
user serviceable parts. QUALIFIED SERVICE PERSONNEL ONLY must 
perform the maintenance and the battery replacement for this UPS system. 

 

1.2. 

Life Support Policy

 

 

As a general policy, we do not recommend the use of any of our products in 
life support applications where failure or malfunction of the product can be 
reasonably expected to cause failure of the life support device or to 
significantly affect its safety or effectiveness. We do not recommend the use 
of any of our products in direct patient care. We will not knowingly sell our 
products for use in such applications unless it receives in writing assurances 
satisfactory to us that (a) the risks of injury or damage have been minimized,   
(b) the customer assumes all such risks, and (c) our liability is adequately 
protected under the circumstances. 

 

1.3. 

FCC Notice 

 

This equipment has been tested and found to comply with the limits for a 
Class A computing device in accordance with the specifications in Subpart J 
of Part 15 of FCC Rules and the Class A limits for radio noise emissions from 
digital apparatus set out in the Radio Interference of the Canadian 
Department of Communications. 

Summary of Contents for ED6200RM

Page 1: ...tems Inc 1455 LeMay Drive Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000315 R5 ED6200RM Parallel Redundant ON LINE SERIES User...

Page 2: ...Installation of Castor Covers 14 3 5 Wiring the Input and Output Connections 18 3 6 RJ 45 cables for the Maintenance Bypass Operation 27 3 7 Operation and Setup Instructions 28 4 Communication Port EP...

Page 3: ...enance of the UPS and batteries 1 1 12 CAUTION A disconnect switch must be provided by the user for the AC output circuit when the UPS s output is hardwired To reduce the risk of fire connect only to...

Page 4: ...Parallel Redundant kit Contact your local distributor for more information concerning the Parallel Redundant operation 2 2 5 Maintenance Bypass Switch which reduces down time for maintenance 2 2 6 The...

Page 5: ...Er03 PFC Boost soft start abnormal after 30 seconds 30 Er04 Inverter Failure 31 Er05 Battery Weak or Dead 32 Er06 Output Short Circuit 33 Er08 DC Bus high voltage level abnormal 34 Er09 DC Bus low vol...

Page 6: ...59 CEr2 Bypass Voltage out of range 60 CEr3 Inverter Voltage out of range 61 CEr4 Load Percentage out of range 62 CEr5 Battery Voltage out of range 63 CEr6 UPS Output Voltage out of range Er7 Er19 Er2...

Page 7: ...nnecting a Battery Pack G Cooling Fans H Terminal block for Input Output power connection I Option Slot 1 is for other option cards except the SNMP card and the Programmable Relay card J Option Slot 2...

Page 8: ...cking material Since the manufacturer is not responsible for shipping damage incurred when the system is returned the original packing material is inexpensive insurance PLEASE SAVE THE PACKING MATERIA...

Page 9: ...Pack and then connect UPS and the Battery Pack together S1 A3 S3 15 3 4 1 2 UPS Isolation Transformer and Battery Pack 3 4 2 Rack Installation 3 4 2 1 UPS Isolation Transformer and Battery Pack Step1...

Page 10: ...ion Transformer and Battery Pack Step3 Install the Rails in the 4 post Rack S3 S3 17 Step4 Install the Battery Pack to the Rails Step5 Install the Rails in the 4 post Rack and then install the Isolati...

Page 11: ...current protection device in accordance with the National Electric Code ANSI NFPA 70 Use 60 C copper wire and apply 22 1lb in of torque force when connecting to the terminal blocks Output Voltage and...

Page 12: ...put of the Isolation Transformer A Qualified Electrical Contractor must perform the hardwiring The outputs must be connected to an over current protection device circuit breaker in accordance with the...

Page 13: ...rom L22 to N11 L11 L1 N22 L2 G Earth Ground 240Vac 23 3 5 2 3 9 Configuration 5 Output Two separate circuits of 120VAC 3KVA loads 3KVA max load per circuit Total combined output load not to exceed 6KV...

Page 14: ...e box to the TR OUTPUT terminal block 4 Has a Maintenance Bypass Switch see Section 3 6 for connecting the RJ 45 cables for the Maintenance Bypass operation 25 3 5 3 1 Application B 1 Utility Input 20...

Page 15: ...L21 2 Connect a wire to the Output terminal N22 3 Connect a wire to the Output terminal G2 3 5 4 3 Application D 1 Utility Input 208 240VAC must be hardwired see Section 3 5 4 1 for wiring 2 UPS Outpu...

Page 16: ...n Switch on the front panel for approximately 3 seconds then release The audible alarm will sound 2 beeps then the LCD display will change from drawing B to drawing C C 29 3 7 1 6 The UPS will perform...

Page 17: ...release the audible alarm will sound 2 beeps The LCD display will change from drawing G to drawing H the UPS will be in self test mode The UPS will provide an output within approximately 1 minute and...

Page 18: ...1 Once the UPS has successfully started up press the Special Function keypad to change the LCD display screen to drawing Q1 Q1 It shows the Buzzer is Enabled Q2 It shows the Buzzer is Disabled 3 7 4 2...

Page 19: ...ws the bypass voltage is adjusted to the higher limit T It shows the Frequency Window is 3Hz 35 U It shows the Inverter Output Voltage setting V1 It shows the UPS is operated in the Normal mode V2 It...

Page 20: ...can be changed to 184VAC 260VAC or 195VAC 260VAC 3 7 5 4 Drawing T means the bypass frequency window of the Inverter Output can be changed to 3Hz or 1Hz 3 7 5 5 Drawing U means the Inverter Output Vo...

Page 21: ...PS system 3 7 8 1 1 Press the Off switch for approximately 5 seconds the LCD screen will display drawing B and the UPS will be in the Bypass mode 3 7 8 1 2 Remove the Maintenance Bypass Switch cover f...

Page 22: ...UPS shuts down the fans will still be on In approximately 1 minute the fans will reduce speed To restart the UPS once the utility power returns Press the Off switch on the front panel for 2 beeps then...

Page 23: ...43 7 Replacing the Batteries QUALIFIED SERVICE PERSONNEL ONLY Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries WARNING This Uninterruptible Power Supply contains...

Page 24: ...el of the UPS 7 1 4 Turn Off the utility power circuit breaker at the service panel 7 1 5 Disconnect all of the communications and network cables from the rear panel of the UPS 7 1 6 Turn Off the DC c...

Page 25: ...reaker on the rear panel of the UPS if applicable 7 1 34 Press and hold the On Switch on the front panel for approximately 3 seconds then release if applicable 7 1 35 Turn On the equipment that is con...

Page 26: ...tripped A tripped circuit breaker is the most common problem Call your dealer for assistance If you cannot reach your dealer or if they cannot resolve the problem call or fax MINUTEMAN Technical Suppo...

Page 27: ...Except as provided herein Para Systems makes no warranties expressed or implied including warranties of merchantability and fitness for a particular purpose Some states do not permit limitation of imp...

Reviews: