22
3.5.2.3.7 Configuration
3.
Output: 240VAC 6KVA load and two separate circuits of 120VAC 3KVA loads
(3KVA max load per circuit). Total combined output load not to exceed 6KVA.
Connect a jumper wire from L22 to N11.
Circuit1: L22-Line, N22-Neutral, G-Earth Ground.
Circuit2: L11-Line, N11-Neutral, G-Earth Ground.
Circuit3: L11-L1, N22-L2, G-Earth Ground.
3.5.2.3.8 Configuration
4.
Output: 240VAC single 6KVA load. Total output load not to exceed 6KVA.
Connect a jumper wire from L22 to N11.
L11-L1, N22-L2, G-Earth Ground.
240Vac
23
3.5.2.3.9 Configuration
5.
Output: Two separate circuits of 120VAC 3KVA loads (3KVA max load per
circuit). Total combined output load not to exceed 6KVA.
Circuit1: L22-Line, N22-Neutral, G-Earth Ground.
Circuit2: L11-Line, N11-Neutral, G-Earth Ground.
120Vac
120Vac
3.5.2.3.10 Configuration 6.
Output: 120VAC single 6KVA load. Total output load not to exceed 6KVA.
Connect a jumper wire from N22 to N11 and another jumper wire from L22 to
L11. L11-Line, N11-Neutral, G-Earth Ground.
NOTE:
Use an over-current protection device (circuit breaker) of 50 amperes
and No. 6 AWG, 60
°
C copper wire when using this configuration.
120Vac