background image

Page 5 of 12

6. INDEX & DOWN ARROW:

Pressing these keys simultaneously will allow backing up

one menu item, or if at the first menu item they will cause the display to return to the
PRIMARY MENU.  If an alarm condition has occurred, these keys may be used to reset
the alarm.

7. INDEX & ENTER:

Pressing these keys simultaneously and holding them for 5

seconds allows recovery from the various error messages.  The following menu items
will be reset:

ALiH: Alarm inhibit

OPEn InP: Thermocouple error message

bAd InP: RTD error message

CHEC CAL: Check calibration error message

Correct the problems associated with the above conditions first before using these reset
keys. More than one error could be present. Caution is advised since several items are
reset at one time.

While in the PRIMARY or SECONDARY MENU, if no key is pressed for a period of 30
seconds, the display will return to the HOME position displaying the temperature value. The
time is increased to 1 minute when in the SECURE MENU.

NOTE:

To move to the PRIMARY MENU quickly from any other menu, press the UP

ARROW & ENTER keys followed by pressing the INDEX DOWN ARROW keys.

SECURITY LEVEL SELECTION

NOTE:  Lock menus to prevent unauthorized changes to controller settings.
Four levels of security are provided. The security level can be changed under SECr in the
SECURE MENU.  The display shows the current security level.  Refer to the password table
below for the correct value to enter for the security level desired.  To change security levels,
set the password value using the UP & DOWN ARROW keys and press the ENTER key.
The SECr menu item's security level may be viewed or changed at any time regardless of
the present security level. The password values shown in the table cannot be altered, so
retain a copy of this page for future reference. This will be the only reference made to
password values in this instruction book.

PASSWORD  TABLE

DISPLAYED VALUE

WHEN VIEWED

1

2

3

4

SECURITY LEVEL

MENU

SECURITY

Primary

Locked

Secondary

Locked

Secure

Locked

Primary

Unlocked

Secondary

Locked

Secure

Locked

Primary

Unlocked

Secondary

Unlocked

Secure

Locked

Primary

Unlocked

Secondary

Unlocked

Secure

Unlocked

PASSWORD

VALUE TO ENTER

1110

1101

1011

111

Page 8 of 12

InPt

Input Fault Timer: Select OFF, 0.1 to 540.0 minutes. Whenever an Input is out of
range (UFL or OFL displayed), shorted, or open the timer will start. When the time
has elapsed, the controller will revert to a safe condition (Output Off, Flashing
Display). If OFF is selected, the Input Fault Timer will not be recognized (time =
infinite).

SPL

Set Point Low: Select from the lowest input range value to SPH value. This will set
the minimum SP  value that can be entered. The value for SP will stop moving when
this value is reached.

SPH

Set Point High: Select from the highest input range value to SPL value. This will set
the maximum SP value that can be entered. The value for SP will stop moving when
this value is reached.

SPSt Set Point State: Select dir or rE.

dir

Direct Action. As the input increases the output will increase. Most com-
monly used in cooling processes.

rE

Reverse Action. As the input increases the output will decrease. Most
commonly used in heating processes.

SPOL Set Point Output Low Limit: Select to 100% but not greater than SPOH. This item

limits the lowest output value.  This is useful for adding a bias to the process when
needed.

SPOH Set Point Output High Limit: Select 0 to 100% but not less than SPOL. This item

allows setting the maximum output limit. This is useful with processes that are over-
powered.

SPLP Set Point Lamp: Select O on or OoFF.

O on

Lamp ON when Output is ON.

OoFF Lamp OFF when Output is ON.

ALARM TYPE AND ACTION (if present)

Caution: In any critical application where failure could cause expensive

product loss or endanger personal safety, a redundant limit controller is
required.

When setting an alarm value for an absolute alarm (ALt = AbS), simply set the value at
which the alarm is to occur.

When setting the alarm value for a deviation alarm (ALt = dE), set the difference in value
from the Set Point (SP) desired. For example, if a low alarm is required to be 5 degrees
below the SP, then set ALLo to -5. If a high alarm is required 20 degrees above the SP, then
set ALHi to +20. If SP is changed, the alarm will continue to hold the same relationship as
originally set.

The diagram at the top of the next page shows the action and reset functions for both
absolute and deviation alarms.

When Alarm Power Interrupt, ALPi, is programmed ON and Alarm Reset, ALrE, is
programmed for Hold, the alarm will automatically reset upon a power failure and
subsequent restoration if no alarm condition is present.

If Alarm Inhibit, ALiH, is selected ON, an alarm condition is suspended upon power up until
the process value passes through the alarm set point once. Alarm inhibit can be restored
as if a power up took place by pressing both the INDEX and ENTER keys for 5 seconds.

Warning: Resetting a high alarm inhibit will not cause an alarm to occur
if the Process Value does not first drop below the high alarm setting.  Do

not use the Alarm Inhibit feature if a hazard is created by this action.  Be
sure to test all combinations of high and low alarm inhibit actions before
placing control into operation.

Summary of Contents for CT15 Series

Page 1: ...TIONS FOR THE CT15 SERIES MICROPROCESSOR BASED TEMPERATURE CONTROLLER MODEL IDENTIFICATION Alarm 0 No 1 Yes Input 1 Thermocouple J K T 2 100 Platinum RTD DIN element PD Model CT15 Output 1 SSR 2 5 VDC...

Page 2: ...he factory programmed for type J thermocouples Suppose for this example you wish to change the input to type K and limit the set point range between 0 and 1000 C First entertheSECUREMENUasinstructedon...

Page 3: ...the front of the panel slide the housing through the cut out The housing gasket should be against the housing flange before installing From the rear of the panel slide themountingcollaroverthehous ing...

Page 4: ...ons are as follows 1 INDEX Pressing the INDEX key advances the display to the next menu item May also be used in conjunction with other keys as noted below 2 UP ARROW Increments a value changes a menu...

Page 5: ...MARY MENU quickly from any other menu press the UP ARROW ENTER keys followed by pressing the INDEX DOWN ARROW keys SECURITY LEVEL SELECTION NOTE Lock menus to prevent unauthorized changes to controlle...

Page 6: ...tioning Control is adjustable in 1 sec steps Recommended for mechanical outputs relays solenoids etc For best contact life a time should be selected that is as long as possible without causing the pro...

Page 7: ...constant When the 0 1 degree resolution is selected this should be increased to 4 If this value is set too high controllability will suffer SECURE MENU Hold UPARROW ENTERfor5Seconds PressINDEXtoadvan...

Page 8: ...FF Lamp OFF when Output is ON ALARM TYPE AND ACTION if present Caution In any critical application where failure could cause expensive product loss or endanger personal safety a redundant limit contro...

Page 9: ...anged the Alarm Point will track with SP ALrE Alarm Reset Select OnOF or Hold OnOF Automatic Reset Hold ManualReset Acknowledge reset bysimultaneouslypressingtheINDEX DOWN ARROW keys for 5 sec ALPi Al...

Page 10: ...OFL bAd InP OPEn InP CHEC CAL No dis play lighted FAIL tESt CHEC SP CHEC ALLO CHEC ALHi CHEC SPL or CHEC SPH MEANING Underflow or Overflow Process value has ex ceeded input range ends UFLorOFLwillseq...

Page 11: ...bility 0 05 over the supply voltage range Temperature Stability 4 V C 2 3 V F typical 8 V C 4 5 V F maximum Common Mode Rejection 140 db minimum at 60 Hz Normal Mode Rejection 65 db typical 60 db at 6...

Page 12: ...th Seller s instructions and the defect is not caused by shipping damage misuse or abuse by the Buyer There are no other warranties written oral or implied The liability of the Seller is limited to th...

Reviews: