![Minco CT15 Series Instructions Manual Download Page 11](http://html1.mh-extra.com/html/minco/ct15-series/ct15-series_instructions-manual_1800599011.webp)
Page 2 of 12
TABLE OF CONTENTS
INPUT WIRING ....................................................................................................................... 3
INSTALLATION ....................................................................................................................... 3
WIRING ................................................................................................................................... 4
FRONT PANEL KEY FUNCTIONS .......................................................................................... 4
SECURITY LEVEL SELECTION ............................................................................................. 5
MENU SELECTIONS ............................................................................................................. 6
PRIMARY MENU ..................................................................................................................... 6
SECONDARY MENU .............................................................................................................. 6
SECURE MENU ...................................................................................................................... 7
ALARM TYPE AND ACTION ................................................................................................... 8
DIAGNOSTIC ERROR MESSAGES ..................................................................................... 10
SPECIFICATIONS ................................................................................................................. 11
DIMENSIONS ........................................................................................................................ 12
GETTING STARTED
1. Install the control as described on page 3.
2. Wire your control following the instructions on page 3 and drawing on page 4.
3. Most controls do not need many (if any) program changes to work on your process. For best
results if programming changes are necessary, make all the necessary changes in the
SECURE MENU (page 7) before making changes to the SECONDARY MENU (page 6). If
error messages occur, check the Diagnostic Error Messages on page 10 for help.
Take the example of a Model CT15011 that comes from the factory programmed for type J
thermocouples. Suppose for this example you wish to change the input to type K and limit the
set point range between 0° and 1000° C.
First, enter the SECURE MENU as instructed on page 7. Press the INDEX key until the display
shows Inp and press the DOWN ARROW until the display shows CA. Don't forget to press the
ENTER key to retain your setting.
Next, press the INDEX key to display F-C. Press the DOWN ARROW until the display shows C.
Press ENTER.
Next, press the INDEX key until SPL is displayed (pass the dPt and InPt selections). Press the
UP ARROW until the display shows 0. Press ENTER.
Finally, press INDEX key to display SPH. Press the DOWN ARROW until the display shows
1000. Press ENTER.
The necessary program changes are now complete. After 30 seconds the display will switch
back to the temperature reading. If you want to return faster, press the UP ARROW and ENTER
keys (at the same time) and then press the DOWN ARROW and INDEX keys ( again at the same
time). This will 'back out' of the menu and immediately display the temperature reading.
Page 11 of 12
Input Type
-
Temperature
Range & Unit
of measure
1°F
1°C
Type J
Iron-
Constantan
-100 to +1600
-73 to +871
Type K
Chromel-
Alumel
-200 to +2500
-129 to +1371
Type T
Copper-
Constantan
-350 to +750
-212 to +398
Input Ranges (as ordered)
Thermocouple Types
SPECIFICATIONS
Selectable Inputs: Thermocouple or RTD as ordered.
Input Impedance:
Thermocouple = 3 megohms minimum.
RTD current = 200 uA.
Sensor Break Protection: De-energizes control output to protect system.
Set Point Range: Selectable (See range chart above).
Display: One; 4 digit, 7 segment, 0.3" high LEDs.
Control Action: Selectable for Reverse (usually heating) or Direct (usually cooling).
Ramp: One ramp time adjustable from 0 to 100 hours.
Proportional Band: 5 to 5000 °F or equivalent °C.
Reset Time (Integral): Off or 0.1 to 99.9 minutes.
Rate Time (Derivative): Off or 0.01 to 99.99 minutes.
Cycle Rate: 1 to 80 seconds, and on-off.
On - Off Differential: Adjustable 1° F to 999°F in 1° steps (equivalent °C).
Alarm On - Off Differential: 2° F or equivalent in °C.
Accuracy: ±0.25% of span, ±1 degree.
Resolution: 1 degree or 0.1 degree, selectable.
Line Voltage Stability: ±0.05% over the supply voltage range.
Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F) maximum.
Common Mode Rejection: 140 db minimum at 60 Hz.
Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
Isolation: Relay and SSR outputs are isolated. 5VDC output must not share a common
ground with the input.
Supply Voltage: 100 to 240 VAC, nom., +10 -15%, 50 to 400 Hz. single phase; 132 to 240
VDC, nom., +10 -20%.
Power Consumption: 5VA maximum.
Operating Temperature Range: -10 to +55 °C (+14 to 131 °F).
Storage Temperature Range: -40 to +80 °C (-40 to 176 °F).
Operating Humidity Range: 0 to 90% up to 40 °C non-condensing. 10 to 50% at 55 °C
non-condensing.
Memory Backup: Non-volatile memory. No batteries required.
Control Output Ratings:
1. SSR, 3.5 A @ 250 VAC at 25 °C. Derates to 1.25 A @ 55 °C. Minimum 48 VAC and
100 mA required.
2. Switched voltage (non-isolated): 5 VDC @ 25 mA.
3. Relay, Form A contact (SPST), 3 A @ 250 VAC resistive; 1.5 A @ 250 VAC inductive;
Pilot Duty Rating: 250 VA, 2 A @ 125 VAC or 1 A @ 250 VAC.
Alarm Relay Rating: Same as Control Output Relay.
Weight: 227 g (8 oz).
Agency Approvals: UL E83725, and CSA LR40125.
Front Panel Rating (non-hazardous locations): Designed to meet UL 4X for non-
hazardous locations (equal to NEMA rating).
100 Ohm Platinum
0.00385 DIN Curve
element code PD
-328 to +1607
-200 to +875
RTD Type