43
Possible
Causes
1. MIN SPD and MAX
SPD not calibrated.
2. Field not operating
properly.
1. MAX SPD setting is
too low.
2. IR COMP setting is
too low.
3. Motor is overloaded.
1. IR COMP is set too
high.
2. Motor bouncing in
and out of TORQUE
limit.
Suggested
Solutions
1. Calibrate MIN SPD
and MAX SPD (page
28).
2. Check motor field
connections and
voltage.
1. Increase MAX SPD
setting (page 28).
2. Increase IR COMP
setting (page 29).
3. Check motor load.
Resize the motor and
drive if necessary.
1. Adjust the IR COMP
setting slightly CCW
until the motor speed
stabilizes (page 29).
2. Make sure motor is
not undersized for
load; adjust
TORQUE pot CW
(page 30).
Problem
Motor runs too slow or
too fast.
Motor will not reach the
desired speed.
Motor pulsates or
surges under load.
Troubleshooting