8
MM-PCM Series
Shielding Guidelines
As a general rule, Minarik Drives recommends shielding of all conductors.
If it is not practical to shield power conductors, it is recommended
to shield all logic-level leads. If shielding of all logic-level leads is not
practical, the user should twist all logic leads with themselves to
minimize induced noise.
It may be necessary to earth ground the shielded cable. If noise is
produced by devices other than the drive, ground the shield at the drive
end. If noise is generated by a device on the drive, ground the shield at
the end away from the drive. Do not ground both ends of the shield.
If the drive continues to pick up noise after grounding the shield, it may
be necessary to add AC line filtering devices, or to mount the drive in a
less noisy environment.
Logic wires from other input devices, such as motion controllers and PLL
velocity controllers, must be separated from power lines in the same
manner as the logic I/O on this drive.
Under no circumstances should power and logic level leads be
bundled together. Induced voltage can cause unpredictable
behavior in any electronic device, including motor controls.
!
WARNING!