background image

GSA

 

Gas-Fired Steam Boilers – 

Boiler Manual

4

Part Number 550-110-738/1012

1  Prepare boiler location  

continued

Vent System

  Failure to follow all instructions can result in flue gas 

spillage and carbon monoxide emissions, causing 

severe personal injury or death.

  Inspect  existing  chimney  before  installing  boiler. 

Failure  to  clean  or  replace  perforated  pipe  or  tile 

lining will cause severe personal injury or death.

  Do not alter boiler draft hood or place any obstruc-

tion or non-certified vent damper in breeching or 

vent  system.  CSA  certification  will  become  void. 

Flue gas spillage and carbon monoxide emissions 

will occur causing severe personal injury or death.

  The following requirements apply when you remove 

an existing boiler from a vent system shared with 

other appliances. 

If the new boiler will not use the 

common vent, you must test (as described below) 

each remaining appliance — operating by itself — to 

verify that the vent system operates adequately.

When removing boiler from existing common vent 

system:

At the time of removal of an existing boiler, the following steps 

shall  be  followed  with  each  appliance  remaining  connected  to 

the common venting system placed in operation, while the other 

appliances remaining connected to the common venting system 

are not in operation.
a.  Seal any unused openings in the common venting system.
b.  Visually  inspect  the  venting  system  for  proper  size  and 

horizontal  pitch  and  determine  there  is  no  blockage  or 

restriction, leakage, corrosion or other deficiencies which could 

cause an unsafe condition.

c.  Test vent system — Insofar as is practical, close all building 

doors and windows and all doors between the space in which 

the appliances remaining connected to the common venting 

system  are  located  and  other  spaces  of  the  building. Turn 

on clothes dryers and any appliance not connected to the 

common venting system. Turn on any exhaust fans, such as 

range hoods and bathroom exhausts, so they will operate at 

maximum speed. Do not operate a summer exhaust fan. Close 

fireplace dampers.

d.  Place in operation the appliance being inspected. Follow the 

operating  instructions.    Adjust  thermostat  so  appliance  will 

operate continuously.

e.  Test  for  spillage at  draft  hood  relief  opening  after  5 min-

utes of main burner operation. Use the flame of a match or 

candle.

f.  After it has been determined that each appliance remaining 

connected to the common venting system properly vents when 

tested as outlined above, return doors, windows, exhaust fans, 

fireplace dampers, and any other gas-burning appliance to 

their previous conditions of use.

Any improper operation of the common venting system should be 

corrected so the installation conforms with the National Fuel Gas 

Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation 

Codes. When resizing any portion of the common venting sys-

tem, the common venting system should be resized to approach 

the minimum size as determined using the appropriate tables 

in  the  National  Fuel  Gas  Code,  ANSI Z223.1/NFPA 54  and/or 

CANCGA B149, Installation Codes.

Residential garage installation

Take the following special precautions when installing the boiler in 

a residential garage. If the boiler is located in a residential garage, 

per ANSI Z223.1:
•  Mount the boiler a minimum of 18 inches above the floor of 

the garage to assure the burner and ignition devices will be 

no less than 18 inches above the floor.

•  Locate  or  protect  the  boiler  so it cannot  be damaged by a 

moving vehicle.

Flooring and foundation

  Do  not  install  boiler  on  combustible  flooring  or 

carpeting even if a concrete or aerated foundation 

is used. Fire can result, causing severe personal 

injury, death or substantial property damage.

1.   Provide a  solid  brick  or  minimum  2‑inch  thick  concrete 

foundation pad if any of the following is true:
•  floor can become flooded.
•  the boiler mounting area is not level.

2.  See Table 1 for minimum foundation dimensions.
3.  Use a foundation with airways when:

•  Electrical wiring or telephone cables buried in the concrete 

floor of the boiler room.

•  Concrete floor is “green”.
•  Water is channeled under the concrete.

Boiler 

model

Minimum

foundation

length

Minimum

foundation  

“L” width

GSA-075 –– GSA-100

29 ⅝”

19”

GSA-125 –– GSA-150

29 ⅝”

23 ¼”

GSA-175 –– GSA-200

29 ⅝”

27 ½”

GSA-250

29 ⅝”

31 ¾”

GSA-300

29 ⅝”

36”

Table 1   

  Minimum foundation size

Summary of Contents for GSA-075

Page 1: ... property damage INSTALLER Read all instructions before install ing Read page 2 first Follow all instructions in proper order to prevent personal injury or death Consider piping and installation when determining boiler location Any claims for damage or shortage in shipment must be filed immediately against the transporta tion company by the consignee GSA boilers cannot be adapted for heater use Ha...

Page 2: ...ing or sealing compounds in boiler system Water seal deterioration will occur causing leakage between boiler sections circulator flanges diaphragm tanks or other system components This can result in substantial property damage 7 DO NOT use homemade cures or boiler patent medicines Serious damage to boiler personnel and or property may result 8 Continual fresh makeup water will reduce boiler life M...

Page 3: ...s to boiler and system components 2 Clearances to Type B vent materials are as specified by the vent manufacturer Alcove not closet installations only GSA boilers are not approved for closet installation only for alcove installation with minimum clearances to combustible surfaces as shown in the table at right See Figure 1 The front side must be completely open that is a 3 walled room Clearance fo...

Page 4: ... Place in operation the appliance being inspected Follow the operating instructions Adjust thermostat so appliance will operate continuously e Test for spillage at draft hood relief opening after 5 min utes of main burner operation Use the flame of a match or candle f After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as out...

Page 5: ...eous tile linings with joints that prevent retention of moisture and linings made of noncorrosive materials are best Advice for flue connections and chimney linings can be obtained from local gas utility Type B double wall metal vent pipe or single wall vent pipe may be used as a liner 4 Cold masonry chimneys also known as outside chimneys typically have one or more walls exposed to outside air Wh...

Page 6: ...gs gasketed AND Weather stripping has been added on openable windows and doors AND Caulking or sealants are applied to areas such as joints around windows and door frames between sole plates and floors between wall ceiling joints between wall panels at penetrations for plumbing electrical and gas lines and in other openings Tight construction requirements If building is of tight construction and a...

Page 7: ...ll could expand and cause excessive pressure resulting in severe personal injury death or substantial property damage 2 Check for stable gauge pressure for more than 10 minutes Visually check for leaks if gauge pressure drops Do not use petroleum based cleaning or sealing compounds in boiler system Severe damage to boiler will result causing substantial property damage 2 Retest boiler after repair...

Page 8: ...stantial property damage 7 Install rollout thermal fuse element with wire termi nals facing up on front access panel as shown in Figure 10 Wire per the appropriate Control Supple ment Inspect burners GSA 300 boiler 1 All units except GSA 300 are factory assembled but the burners and base panels should be inspected to ensure they are in good condition 2 Remove the access panel Figure 10 and inspect...

Page 9: ... CSA certification will become void Flue gas spillage and carbon monoxide emissions will occur causing severe personal injury or death Screw 10 32 x 3 8 Screw 6 x Boiler cement Access panel Rollout TFE 63904 GSA GSA 300 P Burner Pilot burner Pilot Legend P Figure 10 Access panel Figure 9 Burner drawer installation Figure 8 Burner and pilot burner location Figure 7 Burner drawer assembly Figure 6 F...

Page 10: ...his dimension Do not modify draft hood or vent damper or make another connection between draft hood and vent damper or boiler except as noted below This will void CSA certification and will not be covered by warranty Any changes will cause severe personal injury death or substantial property damage 2 Prepare boiler continued 5 Plug damper harness receptacle into damper harness plug Bypassing jumpe...

Page 11: ...e conden sate return is not adequate refer to recommendations on page 13 Figure 12 Recommended piping piping for parallel flow systems only see Table 6 for recommended sizing Table 6 Recommended pipe sizing Connecting to counterflow piping Apply the recommended piping in Figures 12 and 14 only when connecting to a parallel flow system When connecting to a counterflow system the boiler steam supply...

Page 12: ...ons including the valve inlet are clean and free from any foreign matter Mount the relief valve only in the vertical position directly connected to the tapping designated in the manual on top of the boiler Use pipe compound sparingly or tape on external threads only Do not use a pipe wrench Use proper type and size wrench on wrench pads only Install relief valve in tapping on top of boiler See Tab...

Page 13: ...Measure length of time from when condensate begins to return to when it stops returning Divide this time by 2 5 Add time measured in step 3 to time calculated in step 4 This sum is the average time required for condensate to return to the boiler 6 If this total time is 10 minutes or less no reservoir pipe is needed If total time for condensate to return to boiler from step 5 is more than 10 minute...

Page 14: ... Supple ment Figure 15 Controls Float type low water cutoff when provided by others 1 Install low water cutoff as shown in Figure 16 below SeeTable 4 and Figure 3 on page 7 for actual tapping location 2 Install blowdown line in bottom of cutoff See control manufacturer s instructions for details Pipe blowdown line near floor close to floor drain to eliminate potential of severe burns Do not plug v...

Page 15: ...ly to male threads of pipe joints so that pipe dope does not block gas flow Failure to apply pipe dope as described in this manual can result in severe personal injury death or substantial property damage Table 9 Pipe capacity for 0 60 specific gravity natural gas Natural Gas 1 See Table 9 for pipe length and diameter Base on rated boiler input found on page 31 divide by 1 000 to obtain cubic feet...

Page 16: ... and any local codes Wiring connections Boiler is shipped with controls completely wired except spill switch and vent damper See wiring diagram in the GSA Spark Ignition Control Supplement Thermostat 1 Connect thermostat as shown on wiring diagram on boiler 2 Install on inside wall away from influences of drafts hot or cold water pipes lighting fixtures television sunrays or fireplaces 3 If thermo...

Page 17: ...l except for leakage tests until boiler is ready to be fired 2 Fill to normal waterline halfway up gauge glass 3 Boiler water pH 7 0 to 8 5 is recommended 4 Follow skimming procedure right Skimming the boiler Clean all newly installed steam boilers to remove oil and grease Failure to properly clean can result in violent fluctuations of water level water passing into steam mains or high maintenance...

Page 18: ...and repair immediately 2 Inspect vent system thoroughly for signs of deterioration from corrosion physical damage or sagging Verify that masonry chimney liners are in good condition with no obstructions and there are no openings into the chimney 3 Check around the boiler for gas odor following the procedure of Check for gas leaks page 17 4 Verify operation using procedures below Perform Checkout p...

Page 19: ...er operation 1 Raise room thermostat to call for heat Vent damper actuator will slowly open vent damper 2 When vent damper is fully open Main gas valve will open and main burners will ignite Vent damper must be fully open before main burn ers light If vent damper does not fully open flue products such as carbon monoxide will escape into house causing severe personal injury or death 3 Lower thermos...

Page 20: ...____________________________ ______________________________ company address phone _____________________________________ installer s signature o Installation instructions have been followed o Check out sequence has been performed o Above information is certified to be correct o Information received and left with owner maintenance person Spark ignition boilers Connect manometer to outlet side of gas...

Page 21: ...terline Limit controls and cutoffs Boiler relief valve Review Review with owner Daily Check boiler area Check boiler pressure gauge Check air openings Monthly Check boiler and system piping Check venting system Check operate boiler relief valve Check pilot and main burner flames Periodically Test low water cutoff End of season Shut down procedure Follow the Service and maintenance procedures given...

Page 22: ...cted under Section 7 page 17 of this manual o Inspect Piping 1 Check the boiler interior piping and all system piping for signs of leaks 2 Repair any leaks before proceeding Do not use petroleum based cleaning or sealing compounds in boiler system Severe damage to boiler will occur resulting in substantial property damage Eliminate all system or boiler leaks Continual fresh makeup water will reduc...

Page 23: ...le test per page 15 of this manual if there is any indication of a leak Boiler waterline Normal waterline is halfway up gauge glass Limit controls 1 Inspect and test the boiler limit control Verify operation by turning control set point below boiler pressure Boiler should cycle off Return dial to original setting o Check test Low water cutoffs Probe type low water cutoff see below Clean probe type...

Page 24: ...ng the heating season to verify the valve and discharge piping flow freely If corrosion and or deposits are noticed within the valve body testing must be performed more often A try lever test must also be performed at the end of any non service period Follow the instructions below for a try lever test With the system at operating pressure lift and hold the test lever fully open for at least 5 seco...

Page 25: ...al n Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid n Eye Irrigate immediately n Breathing Fresh air This product contains fiberglass jacket insulation and ceramic fiber materials in combustion chamber lining or base panels in gas fired products Airborne fibers from these materials have been listed by the State of Califor...

Page 26: ...ass and 1 each 3 and 6 square cut seals 381 800 100WT 10 End section right hand 18118 311 800 029WT 11 Intermediate section 1815 311 800 010WT Item number Description Part number 12 Tie rod 1 2 GSA 075 GSA 100 GSA 125 GSA 150 GSA 175 GSA 200 GSA 250 GSA 300 560 234 470WT 560 234 475WT 560 234 480WT 560 234 485WT 560 234 490WT 13 Front base panel insulation in Base insulation kit 14 Base access pan...

Page 27: ...800 155WT 421 800 156WT 3 Jacket panel right side 421 800 151WT 4 Jacket panel door GSA 075 GSA 100 GSA 125 GSA 150 GSA 175 GSA 200 GSA 250 GSA 300 421 800 167WT 421 800 168WT 421 800 169WT 421 800 170WT 421 800 171WT 5 Jacket panel interior GSA 075 GSA 100 GSA 125 GSA 150 GSA 175 GSA 200 GSA 250 GSA 300 421 800 162WT 421 800 163WT 421 800 164WT 421 800 165WT 421 800 166WT 6 Jacket panel rear GSA ...

Page 28: ...GSA Gas Fired Steam Boilers Boiler Manual 28 Part Number 550 110 738 1012 10 Replacement parts continued Figure 22 Controls and trim ...

Page 29: ...GSA Gas Fired Steam Boilers Boiler Manual 29 Part Number 550 110 738 1012 10 Replacement parts continued Figure 23 For Spark Ignition Gas Controls see GSA Spark Ignition Control Supplement ...

Page 30: ...NPT V Damper height inches D Vent diameter inches W Jacket width inches Approximate shipping weight GSA 075 3 2 1 2 6 5 17 430 GSA 100 3 2 1 2 6 5 17 430 GSA 125 3 2 1 2 61 2 6 21 505 GSA 150 3 2 1 2 61 2 6 21 505 GSA 175 3 2 1 2 9 7 25 585 GSA 200 3 2 1 2 9 7 25 585 GSA 250 3 2 3 4 91 2 8 29 660 GSA 300 3 2 3 4 Note 3 Note 3 34 735 Note 2 Size gas piping from meter to boiler per local utility req...

Page 31: ...0 157 500 131 000 454 109 000 11 2 82 8 7 I D x 20 GSA 200 200 000 167 000 180 000 150 000 521 125 000 11 2 82 8 7 I D x 20 GSA 250 250 000 209 000 225 000 188 000 654 157 000 12 6 83 0 8 I D x 20 GSA 300 299 000 247 000 270 000 216 000 770 185 000 14 0 82 4 8 I D x 20 Notes 1 Based on standard test procedures prescribed by the United States Department of Energy 2 Net AHRI ratings are based on net...

Page 32: ...32 Part Number 550 110 738 1012 W T 8201 W Calumet Rd Milwaukee WI 53223 GSA Gas Fired Steam Boilers Boiler Manual ...

Reviews: