MIL'S HOSPITAIR PACK S MVA 8 General Installation And Maintenance Instructions Download Page 18

 

 

General installation and maintenance instructions 

HOSPITAIR PACK S (MV) - 11 bar 

 

Page 17/17 

12/2016 

Manual N° 520003 version 5 

 

The units with PROCOM2 automate can be affected by communication portables or mobiles RF’s equipment. 
 

Recommended separation distances between portable and mobile RF communications equipment and the units

 

WITH 

PROCOM2 AUTOMATE  

The units

 

with PROCOM2 automate is intended for use in an electromagnetic environment in which radiated RF disturbances are 

controlled. The customer or the user of the units

 

with PROCOM2 automate can help prevent electromagnetic interference by 

maintaining a minimum distance between portable and mobile RF communications equipment (transmitters) and the units

 

with 

PROCOM2 automate as recommended below, according to the maximum output power of the communications equipment 

 

Separation distance according to frequency of transmitter

 

Rated maximum 

output 

power of transmitter 

m  

 

150 kHz to 80 MHz  

 

d = 

1.16 

P

 

 

80 MHz to 800 MHz  

 

d = 

1.16 

P

 

 

800 MHz to 2,5 GHz  

 

d =  

2.33 

P

 

0,01  

0.12 

0.12 

0.23 

0,1  

0.37 

0.37 

0.74 

1  

1.16 

1.16 

2.33 

10  

3.69 

3.69 

7.37 

100  

11.6 

11.6 

23.3 

 
For transmitters rated at a maximum output power not listed above, the recommended separation distance 

in meters (m) can be 

determined using the equation applicable to the frequency of the transmitter, where 

is the maximum output power rating of the 

transmitter in watts (W) according to the transmitter manufacturer. 
 
NOTE 1 At 80 MHz and 800 MHz, the separation distance for the higher frequency range applies. 
 
NOTE 2 These guidelines may not apply in all situations. Electromagnetic propagation is affected by absorption and reflection from 
structures, objects and people. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Specifications are subject to be changed without notice 

 

Summary of Contents for HOSPITAIR PACK S MVA 8

Page 1: ...RULES see manual n 511927 Spare parts list and maintenance instructions for compressors First apposition of the EC marking 2009 This document must not be disclosed or reproduced without permission fr...

Page 2: ...ESCRIPTION OF THE OPERATION 5 INSTALLATIONS 7 3 5 DIMENSIONS 7 SECTION 4 ELECTRIC POWER SUPPLY 8 4 1 COMPRESSOR POWER SUPPLY 8 4 2 CONNECTION BETWEEN COMPRESSOR AND PROCOM 2 OF PRO2XY 8 4 3 SUMMARY OF...

Page 3: ...in a safe place and to dispose of it with due care for the environment Dustbin on wheels barred of a cross symbol This symbol indicates that the equipment should not be thrown with domestic waste and...

Page 4: ...2 Specification plates Type Hospitair units Serial number Air dryer type Serial number SECTION 2 CHOICE OF ROOM The unit must be located in a clean non humid non saline dustless and ventilated local w...

Page 5: ...38 37 31 820 1 00 13 500 700 x 700 The person in charge of the installation has overall responsibility of the product environment requirements He is also in charge of setting up methods of struggle ag...

Page 6: ...he pressure before the air treatment unit Then the air enters the filtration chain see the description in the manual concerning the filtration chain At the filtration chain output the air is then stor...

Page 7: ...order given by the oxygen generator 3 4 4 Emergency stop compressor Use the emergency button only in extreme necessity because it stops suddenly the compressor and if the compressor is on charge oil c...

Page 8: ...s HOSPITAIR PACK S MVA 8 MVB 12 MVB 16 HOSPITAIR PACK S MVC 19 MVC 23 HOSPITAIR PACK S MVD 31 MVE 38 MVE 46 3 5 2 Vertical air receivers 500 1000 litres E B A C F 1 2 Soupape Outlet Inlet Pressure gau...

Page 9: ...mpliance with the legislation and regulations in force in your country The wire sections are given for information to 5A mm2 Even so the sections shall be defined by taking contacts with the wire prov...

Page 10: ...report The connection between Alarm report on automate units must be done by the person in charge of the Installation He must control the compliance wiring and proper operation during the final accept...

Page 11: ...rainage system OWAMAT separator used to separate oil and water In compliance with Law No 76 663 dated 19 July 1976 relating to installations classified for protecting the environment Law 92 3 dated 3...

Page 12: ...pen the network outlet valve gradually SECTION 7 CLEANING AND MAINTENANCE IMPORTANT For this operation use all necessary protective measures gloves mask overalls etc then destroy contaminated consumab...

Page 13: ...to stop Check the compressor discharge time before it stops completely 10 to 15 seconds 7 3 Safety relief valve When a relief valve with discharge line operates and must be tested no persons may stand...

Page 14: ...to avoid all forced and tensions and to damp out all vibrations even non visible The base of the receiver will have to support the weight of the receiver including in situation of tests In performing...

Page 15: ...g the compressed air unit object of this technical manual are protected by relief valves as indicated in the table hereafter Component Pressure setting bar Location of the safety relief valve Compress...

Page 16: ...should assure that it is used in such an electromagnetic environment Immunity test IEC 60601 test level Compliance level Electromagnetic environment guidance Electrostatic discharge ESD IEC 61000 4 2...

Page 17: ...ufacturer and d is the recommended separation distance in meters m Field strengths from fixed RF transmitters as determined by an electromagnetic site survey 1 should be less than the compliance level...

Page 18: ...o the maximum output power of the communications equipment Separation distance according to frequency of transmitter Rated maximum output power of transmitter W m 150 kHz to 80 MHz d 1 16 P 80 MHz to...

Page 19: ......

Page 20: ......

Reviews: