MIL'S HOSPITAIR PACK S MVA 8 General Installation And Maintenance Instructions Download Page 13

General installation and maintenance instructions 

HOSPITAIR PACK S (MV) - 11 bar

 

 

 

Manual N° 520003 version 5 

12/2016 

Page 12/17 

 

 
 

 

6 months

12 months  24 months  3 years 

5 years 

COMPRESSOR 

Refer to the maintenance manual 

FILTRATION CHAIN 

Refer to general installation and maintenance 

instructions or maintenance manual 

Electronic drain test 

 

 

 

 

 

PRESSURE INDICATORS (sensor, pressure gauge) 

Measurement validity check 

 

 

 

 

 

Pressure gauge change 

 

 

 

 

 

HYGROMETRY PROBE 

Measurement check or re-calibration 

 

 

 

 

 

RECEIVER 

Call upon an inspection agency 

As per the legislation in force 

ELECTRICAL CABINET 

Clean and dust using a soft brush 

 

 

 

 

 

Check the connections in the cabinet 

 

 

 

 

 

Check the connections at motor terminals 

 

 

 

 

 

Check the intensity of the motors 

 

 

 

 

 

Operate the mechanical back-up system 

 

 

 

 

 

Check the discharge system 

 

 

 

 

 

HOSE 

Overall condition check 

 

 

 

 

 

Change 

 

 

 

 

 

SAFETY VALVE 

Change 

 

 

 

 

 

OWAMAT 

(see the attached OWAMAT manual)

 

Replace the cartridge when water becomes unclear 

 

Note: the maintenance periodicities above are given for reference only and may be increased as required. 
Note: maintenance tables are available for the compressor and the air treatment unit. 

7.1. 

Electronic vent valve test 

A test button is provided at the top of the valve for manual venting. 

For more information, see the attached manual (BEKOMAT 12). 

7.2. Discharge 

system 

When the compressor rotates, make sure that the compressor discharge system operates when pressure reaches 11 
bar or when the order is given to the compressor to stop. 
Check the compressor discharge time before it stops completely (10 to 15 seconds). 

7.3. 

Safety relief valve 

When a relief valve with discharge line operates and must be tested, no persons may stand in front of the valve 
discharge direction. Not allow discharge toxic, explosive or flammable products, into the atmosphere. 
Before the test, a controlled discharge procedure in a confined volume is requested. 
Never tamper with the valve, nor remove the lead/manufacturer's seal, nor modify its adjustment pressure for any 
reason. Not create cold or hot thermal shock on the relief valve. 
Make sure that the lead/manufacturer's seal is never damaged. 
Maintain the valve clean and in functioning order. Check in particular that the exhaust remains free and that no foreign 
body blocks the evacuation piping. 
To make sure that the safety valves continue to operate in good working condition, these must be periodically tested. 
To do this, open the valve manually using the lever or the test knob; this test must be done while keeping the protected 
appliance at a pressure between 80 and 90% of the valve calibration pressure. The valve must open cleanly, and 
release an abundant amount of fluid, and must then close fully once the lever has been released or the knob tightened. 
The operation must be short and performed just once. When an installation is started, initially perform the test 
frequently. 
 
 

SECTION 8.  RECEIVERS (provided by MIL’S) 

Service conditions

: The service conditions are specified on the receiver identification plate. 

The operating pressure should never exceed the service pressure. 
The following minimum and maximum temperatures shall be complied with: 
 

Summary of Contents for HOSPITAIR PACK S MVA 8

Page 1: ...RULES see manual n 511927 Spare parts list and maintenance instructions for compressors First apposition of the EC marking 2009 This document must not be disclosed or reproduced without permission fr...

Page 2: ...ESCRIPTION OF THE OPERATION 5 INSTALLATIONS 7 3 5 DIMENSIONS 7 SECTION 4 ELECTRIC POWER SUPPLY 8 4 1 COMPRESSOR POWER SUPPLY 8 4 2 CONNECTION BETWEEN COMPRESSOR AND PROCOM 2 OF PRO2XY 8 4 3 SUMMARY OF...

Page 3: ...in a safe place and to dispose of it with due care for the environment Dustbin on wheels barred of a cross symbol This symbol indicates that the equipment should not be thrown with domestic waste and...

Page 4: ...2 Specification plates Type Hospitair units Serial number Air dryer type Serial number SECTION 2 CHOICE OF ROOM The unit must be located in a clean non humid non saline dustless and ventilated local w...

Page 5: ...38 37 31 820 1 00 13 500 700 x 700 The person in charge of the installation has overall responsibility of the product environment requirements He is also in charge of setting up methods of struggle ag...

Page 6: ...he pressure before the air treatment unit Then the air enters the filtration chain see the description in the manual concerning the filtration chain At the filtration chain output the air is then stor...

Page 7: ...order given by the oxygen generator 3 4 4 Emergency stop compressor Use the emergency button only in extreme necessity because it stops suddenly the compressor and if the compressor is on charge oil c...

Page 8: ...s HOSPITAIR PACK S MVA 8 MVB 12 MVB 16 HOSPITAIR PACK S MVC 19 MVC 23 HOSPITAIR PACK S MVD 31 MVE 38 MVE 46 3 5 2 Vertical air receivers 500 1000 litres E B A C F 1 2 Soupape Outlet Inlet Pressure gau...

Page 9: ...mpliance with the legislation and regulations in force in your country The wire sections are given for information to 5A mm2 Even so the sections shall be defined by taking contacts with the wire prov...

Page 10: ...report The connection between Alarm report on automate units must be done by the person in charge of the Installation He must control the compliance wiring and proper operation during the final accept...

Page 11: ...rainage system OWAMAT separator used to separate oil and water In compliance with Law No 76 663 dated 19 July 1976 relating to installations classified for protecting the environment Law 92 3 dated 3...

Page 12: ...pen the network outlet valve gradually SECTION 7 CLEANING AND MAINTENANCE IMPORTANT For this operation use all necessary protective measures gloves mask overalls etc then destroy contaminated consumab...

Page 13: ...to stop Check the compressor discharge time before it stops completely 10 to 15 seconds 7 3 Safety relief valve When a relief valve with discharge line operates and must be tested no persons may stand...

Page 14: ...to avoid all forced and tensions and to damp out all vibrations even non visible The base of the receiver will have to support the weight of the receiver including in situation of tests In performing...

Page 15: ...g the compressed air unit object of this technical manual are protected by relief valves as indicated in the table hereafter Component Pressure setting bar Location of the safety relief valve Compress...

Page 16: ...should assure that it is used in such an electromagnetic environment Immunity test IEC 60601 test level Compliance level Electromagnetic environment guidance Electrostatic discharge ESD IEC 61000 4 2...

Page 17: ...ufacturer and d is the recommended separation distance in meters m Field strengths from fixed RF transmitters as determined by an electromagnetic site survey 1 should be less than the compliance level...

Page 18: ...o the maximum output power of the communications equipment Separation distance according to frequency of transmitter Rated maximum output power of transmitter W m 150 kHz to 80 MHz d 1 16 P 80 MHz to...

Page 19: ......

Page 20: ......

Reviews: