.
A complete Parts List is available at www.MillerWelds.com
OM-264 267 Page 16
5-5. Connecting Work Clamp
Ref. 803 640-A
1
Work Clamp
2
Workpiece
Connect work clamp to a clean,
paint-free location on workpiece, as
close to cutting area as possible.
1
2
5-6. Electrical Service Guide
Elec Serv 2014
−
01
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
NOTICE
−
Actual input voltage should not be 10% less than minimum and/or 10% more than maximum input voltages listed in table. If actual input
voltage is outside this range, output may not be be available.
60 Hz Single Phase
Input Voltage (V)
120
240
Input Amperes (A) At Rated Output
A 15 or 20
ampere individual
branch circuit
protected by
time-delay fuses
or circuit breaker
is required.
See Section 4-2
27
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
35
Normal Operating Fuses
3
45
Min Input Conductor Size In AWG
4
10
Max Recommended Input Conductor Length In Feet (Meters)
130
(40)
Min Grounding Conductor Size In AWG
4
10
Reference: 2014 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
5-7. Extension Cord Data
.
When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
Single Phase AC
Input Voltage
Conductor Size
−
AWG (mm
2
)*
6 (13.3)
8 (8.4)
10 (5.3)
12 (3.3)
14 (2.1)
Maximum Allowable Cord Length in ft (m)
120
182 (55)
114 (35)
72 (22)
45 (14)
29 (9)
240
340 (104)
210 (64)
130 (40)
−
−
−
−
*Conductor size is based on maximum 3% voltage drop