Weld Output Terminals And Selecting Cable Sizes
Total Cable (Copper) Length In Weld Circuit Not Exceeding
100 ft (30 m) Or Less
150 ft
(45 m)
200 ft
(60 m)
250 ft
(70 m)
300 ft
(90 m)
350 ft
(105 m)
400 ft
(120 m)
Turn Off power before
connecting to weld output
receptacles.
Welding
Amperes
10 – 60%
Duty
Cycle
60 – 100%
Duty Cycle
10 – 100% Duty Cycle
100
4
4
4
3
2
1
1/0
1/0
150
3
3
2
1
1/0
2/0
3/0
3/0
200
3
2
1
1/0
2/0
3/0
4/0
4/0
Negative
Positive
250
2
1
1/0
2/0
3/0
4/0
2-2/0
2-2/0
Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
S-0007-D
2-8.
Electrical Service Guide
Input Voltage
230
240
Input Amperes At Rated Output
18
17
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
30
30
Reference: 1997 National Electrical Code (NEC)
S-0092-J