OM-463 Page 24
SECTION 6 − OPERATING AUXILIARY EQUIPMENT
6-1.
120 Volt And 240 Volt Duplex Receptacles
Ref. ST-180 933-B
3
2
If unit does not have GFCI re-
ceptacles, use GFCI-pro-
tected extension cord.
1
120 V 15 A AC Receptacle
RC2
2
240 V 15 A AC Receptacle
RC1
Receptacles supply 60 Hz single-
phase power at weld/power speed.
3
Circuit Breakers CB1 And
CB2
CB1 and CB2 protect RC1 and RC2
from overload. If CB1 or CB2
opens, RC1 and one half of RC2
does not work. 120 volts may still be
present at RC1. Press button to re-
set breaker.
If a circuit breaker continues to
open, contact Factory Autho-
rized Service Agent.
Maximum output from each duplex
receptacle is 1.8 kVA/kW, and 3
kVA/kW from all receptacles.
Auxiliary power is not affected
by weld output.
EXAMPLE: If 10 A is drawn from
RC1, only 5 A is available at RC2:
(240 V x 10 A) + (120 V x 5 A) = 3.0
kVA/kW
1