4-8.
Extension Cord Data
When calculating max. cord length, remember to include conductor length from
line disconnect device to input power receptacle.
NOTE
Input Voltage
Input Power
Phase
Hertz
Fuse Size Or
Circuit Breaker Rating
Conductor Size
Max. Cord Length
208 V
3
60
Time-Delay
2
60 A
Normal Operating
3
80 A
8 AWG
89 ft (27 m)
230 V
3
60
Time-Delay
2
60 A
Normal Operating
3
70 A
8 AWG
108 ft (33 m)
460 V
3
60
Time-Delay
2
30 A
Normal Operating
3
35 A
10 AWG
284 ft (87 m)
575 V
3
60
Time-Delay
2
20 A
Normal Operating
3
30 A
12 AWG
268 ft (82 m)
400 V
3
50
Time-Delay
2
25 A
Normal Operating
3
35 A
12 AWG
155 ft (47 m)
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose − no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).